Skip to main content
Schneider Electric LC1F4004V7 — Contactors

Schneider Electric LC1F4004V7 TeSys F Contactor, 500 A AC-1,

MPNLC1F4004V7
Obsolete

Schneider Electric TeSys F contactor, LC1F4004V7, 4-pole NO, 500 A AC-1 rated operational current, 400 V AC 50/60 Hz coil, plate-mount, end-of-life.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1F4004V7 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LC1F4004V7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1
LC1F4004V7 — Contacts & Poles
ParameterValue
Pole configuration4P
LC1F4004V7 — Environmental
ParameterValue
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
LC1F4004V7 — Approvals
ParameterValue
StandardsJIS C8201-4-1 IEC 60947-1 EN 60947-1 IEC 60947-4-1 EN 60947-4-1
LC1F4004V7 — Mechanical
ParameterValue
Width261 mm
Height206 mm
Depth219 mm

Product details

TeSys F 4-Pole Contactor, 500 A AC-1 — End-of-Life Sourcing Note

The Schneider Electric LC1F4004V7 is a TeSys F 4-pole contactor rated 500 A in AC-1 utilisation category (resistive load) at ≤ 440 V and ≤ 40 °C. The 400 V AC coil draws 1075 VA inrush, holding at 15 VA. This is a plate-mount device — no DIN-rail adapter — sized for bolted busbar or lug connections up to 150 mm² per pole.

The 500 A AC-1 rating governs resistive loads like heaters or large lighting banks. For motor duty (AC-3), the contactor would derate significantly — verify against the motor full-load current. The 400 V AC coil operates from 0.85 to 1.1 Uc (340–440 V) and drops out between 0.3 and 0.5 Uc (120–200 V). The 4 NO poles are all normally open; no NC auxiliary is built in, so plan for an external aux block if needed.

Certified to IEC 60947-4-1, EN 60947-4-1, IEC 60947-1, EN 60947-1, and JIS C8201-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1 (1500 V per VDE 0110 group C). Impulse withstand voltage 8 kV, overvoltage category III.

Mounting and Connection

Plate-mount only — no DIN-rail option. Dimensions 261 mm wide × 206 mm high × 219 mm deep. Power connections accept bolted busbar (30 × 5 mm) or lug-ring terminals up to 150 mm². Control circuit uses screw-clamp terminals accepting 1–4 mm² flexible or solid. Tightening torque: 35 N·m on power circuit, 1.2 N·m on control circuit.

Frequently asked questions

How do I get current pricing and availability for LC1F4004V7?

Pricing and availability are confirmed at quote time. Submit an RFQ — the part is sourced through independent distribution and surplus channels on a quoted-to-order basis.

What is LC1F4004V7's listed depth?

The depth is 219 mm.

What is LC1F4004V7's listed range?

It belongs to the TeSys F range of contactors.

What compliance documentation does this brand provide for LC1F4004V7?

The contactor is certified to IEC 60947-4-1, EN 60947-4-1, IEC 60947-1, EN 60947-1, and JIS C8201-4-1. Rated insulation voltage 1000 V per IEC 60947-4-1, impulse withstand 8 kV, overvoltage category III, IP20 front face with shrouds.

MPN
LC1F4004V7