Skip to main content
Schneider Electric LX1D6UP6

Schneider LX1D6UP6 TeSys D Contactor Coil, 230 V AC 60 Hz

MPN LX1D6UP6
Obsolete

Schneider Electric TeSys D series, LX1D6UP6 contactor coil, 230 V AC 60 Hz, for 80 & 95 A contactors.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LX1D6UP6 specifications
ParameterValue
Control circuit typeAC at 60 Hz
Main product or component typeContactor coil
Coil voltage230 V AC 60 Hz
Temp operating max60 °C
Temp operating min-5 °C
Mechanical life cycles10 Mcycles
Operating temperature-5...60 °C

Product details

What this coil is and what it drives

The LX1D6UP6 is a TeSys D replacement coil — the LX1D6 variant — wound for 230 V AC at 60 Hz. It mates specifically with the 80 A and 95 A frame contactors in that family, so if you're swapping a failed coil on an LC1D80 or LC1D95 running on 60 Hz mains, this is the drop-in. Coil draws 220 VA inrush at 60 Hz (cos φ 0.75) and holds at 22 VA (cos φ 0.3), both at 20 °C. That inrush-to-hold ratio is typical for AC-operated contactor coils — the control transformer feeding it needs to handle the inrush without dipping below the 0.85 Uc dropout threshold at 60 Hz. Ambient range is -5 to 60 °C; maximum cycling rate is 3600 operations per hour at 60 °C.

Suppressor note — plan for external RC or varistor

This coil ships without a built-in suppressor module. If the contactor drives inductive loads or shares a control bus with PLC outputs, you will want an external RC snubber or MOV across the coil terminals. The 236.3 Ω DC resistance at 20 °C gives a baseline for sizing the suppression network.

MPN
LX1D6UP6