Schneider Electric LX1D6UP6 — Contactor & Starter Coils

Schneider LX1D6UP6 TeSys D Contactor Coil, 230 V AC 60 Hz

MPNLX1D6UP6
Active

Schneider Electric TeSys D series, LX1D6UP6 contactor coil, 230 V AC 60 Hz, for 80 & 95 A contactors.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LX1D6UP6 — Identification
ParameterValue
Product typeContactor coil
Product rangeTeSys
Device short nameLX1D6
Coil technologyWithout built-in suppressor module
LX1D6UP6 — Electrical
ParameterValue
Control circuit voltage [Uc]230 V AC 60 Hz
Control circuit typeAC at 60 Hz
Control circuit voltage limitsDrop-out: 0.3...0.6 Uc at 50/60 Hz (at Operational: 0.8...1.1 Uc at 50 Hz (at Operational: 0.85...1.1 Uc at 60 Hz (at <55 °C)
Coil resistance (avg.)236.3 Ohm at 20 °C
LX1D6UP6 — Power & Thermal
ParameterValue
Inrush power (VA)220 VA 60 Hz cos phi 0.75 (at 20 °C)
Hold-in power (VA)22 VA 60 Hz cos phi 0.3 (at 20 °C)
Heat dissipation6...10 W at 50/60 Hz
LX1D6UP6 — Performance & Durability
ParameterValue
Max. operating rate3600 cyc/h 60 °C
Mechanical durability10 Mcycles
LX1D6UP6 — Environmental
ParameterValue
Operating temperature-5...60 °C

Product details

What this coil is and what it drives

The LX1D6UP6 is a TeSys D replacement coil — the LX1D6 variant — wound for 230 V AC at 60 Hz. It mates specifically with the 80 A and 95 A frame contactors in that family, so if you're swapping a failed coil on an LC1D80 or LC1D95 running on 60 Hz mains, this is the drop-in. Coil draws 220 VA inrush at 60 Hz (cos φ 0.75) and holds at 22 VA (cos φ 0.3), both at 20 °C. That inrush-to-hold ratio is typical for AC-operated contactor coils — the control transformer feeding it needs to handle the inrush without dipping below the 0.85 Uc dropout threshold at 60 Hz. Ambient range is -5 to 60 °C; maximum cycling rate is 3600 operations per hour at 60 °C.

Suppressor note — plan for external RC or varistor

This coil ships without a built-in suppressor module. If the contactor drives inductive loads or shares a control bus with PLC outputs, you will want an external RC snubber or MOV across the coil terminals. The 236.3 Ω DC resistance at 20 °C gives a baseline for sizing the suppression network.

Frequently asked questions

What contactors does this coil fit?

It is designed for TeSys D contactors rated 80 A and 95 A — the LC1D80 and LC1D95 frames. The coil designation LX1D6 matches that frame size.

Does this coil have a built-in surge suppressor?

No. The coil technology is listed as 'without built-in suppressor module'. An external RC snubber or varistor should be added if the control circuit requires transient suppression.

What is the control voltage and frequency?

230 V AC at 60 Hz. Dropout occurs between 0.3 and 0.6 Uc; pick-up requires 0.85 to 1.1 Uc at 60 Hz below 55 °C.