Skip to main content
Schneider Electric LX9FJ927

TeSys LX9FJ927 Contactor Coil, 125 V AC/DC, Obsolete

MPN LX9FJ927
Obsolete

TeSys F, specific contactor coil, LX9FJ927, 125 V DC low consumption, 125 V AC, 60 ms opening, 20 ms closing, 10 Mcycles mechanical durability.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LX9FJ927 specifications
ParameterValue
Control circuit typeAC 40...400 Hz low consumption DC low consumption
Main product or component typeSpecific contactor coil
Coil voltage125 V DC 125 V AC
Temp operating max55 °C
Temp operating min-5 °C
Mechanical life cycles10 Mcycles
Operating time60 ms opening 20 ms closing
Operating temperature23...131 °F (-5...55 °C)

Product details

Part Identity and Key Specs

The LX9FJ927 is a specific contactor coil from the TeSys F range, designed for use with TeSys F contactors. It operates on a 125 V control circuit, accepting both AC (40...400 Hz) and DC low-consumption supply. Coil opening time is 60 ms, closing time is 20 ms — these switching speeds matter for coordinating with upstream protection and PLC scan cycles. Control voltage limits are operational 0.85...1.1 Uc at 131 °F (55 °C), with drop-out at 0.3...0.5 Uc. This means the coil holds in reliably down to about 106 V on a 125 V nominal supply, and drops out cleanly below about 38 V — important for brownout ride-through and predictable de-energization.

Integration Notes for Panel Builders

This coil has no built-in suppressor module, so an external RC snubber or flyback diode must be added across the coil terminals when driven by a PLC output or solid-state relay. Without suppression, the inductive kick from the 2 H closed-circuit inductance can damage switching contacts or cause EMI issues on the control wiring. Heat dissipation runs 11.4...13.9 W during hold-in — enough to raise temperature inside a crowded enclosure. Allow adequate ventilation or derating when mounting multiple coils side-by-side in a panel. Maximum operating rate is 3600 cycles per hour at 158 °F (70 °C). For high-duty applications like rapid cycling conveyors or press controls, verify the duty cycle stays within this limit to avoid coil overheating.

MPN