Skip to main content
Schneider Electric MGN60506

MGN60506 C60N MCB, 1 A, Curve D, 10 kA, 1P, Multi9

MPN MGN60506
Obsolete

Schneider Electric C60N Multi9 miniature circuit breaker, MGN60506, 1 A rated, curve D, 1 pole, 10 kA breaking capacity at 240 V AC, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60506 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage240 V AC 50/60 Hz phase to neutral
Breaking capacity10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C

All specifications

MGN60506 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The MGN60506 is a C60N miniature circuit breaker from Schneider Electric's Multi9 range — a single-pole, thermal-magnetic MCB rated 1 A at 50 °C, curve D, built to EN/IEC 60947-2 for distribution duty.

The 1 A rating at 50 °C sets the continuous current limit; at higher ambient temperatures derating applies per the standard. Breaking capacity is 10 kA Icu at 240 V AC phase-to-neutral (EN/IEC 60947-2), with a service breaking capacity Ics of 7.5 kA (75 %) at the same voltage — meaning it can safely clear a fault up to that level and still be reused after the event. Rated operational voltage is 240 V AC, single-pole switching, and the device is marked as suitable for isolation (EN/IEC 60947-2) — a required property when the MCB is used as a local disconnect.

Snaps onto 35 mm symmetrical DIN rail. Depth is 73 mm, height 81 mm. Terminals are tunnel type, accepting 1…25 mm² rigid or flexible (with or without ferrule). IP20 finger protection, so it's suited for enclosed distribution boards only — not for wet or dust-laden environments without an outer cabinet.

Meets EN/IEC 60947-2 as a Category A circuit breaker. Earth-leakage protection requires a separate block.

MPN
MGN60506