Skip to main content
Schneider Electric MGN60506 — 1-Pole MCB (DIN Rail)

MGN60506 C60N MCB, 1 A, Curve D, 10 kA, 1P, Multi9

MPNMGN60506
Obsolete

Schneider Electric C60N Multi9 miniature circuit breaker, MGN60506, 1 A rated, curve D, 1 pole, 10 kA breaking capacity at 240 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

MGN60506 — Identification
ParameterValue
Product nameC60
Product / component typeMiniature circuit-breaker
Product rangeMulti9
Device short nameC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
MGN60506 — Electrical & Protection
ParameterValue
Rated current (In)1 A at 50 °C conforming to EN/IEC 60947-2
Rated operational voltage (Ue)240 V AC 50/60 Hz phase to neutral
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 240 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2 3 kA Icu at 415 V AC 50/60 Hz phase to neutral conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
MGN60506 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals1...25 mm² rigid Tunnel type terminals1...25 mm² flexible without cable end Tunnel type terminals1...25 mm² flexible with cable end
Mounting support35 mm symmetrical DIN rail
Mounting modeFixed
Width18 mm
Height81 mm
Depth73 mm
Tightening torque (by circuit)Power circuit: 2 N.m
MGN60506 — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to EN/IEC 60947-2
MGN60506 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2

Product details

The MGN60506 is a C60N miniature circuit breaker from Schneider Electric's Multi9 range — a single-pole, thermal-magnetic MCB rated 1 A at 50 °C, curve D, built to EN/IEC 60947-2 for distribution duty.

The 1 A rating at 50 °C sets the continuous current limit; at higher ambient temperatures derating applies per the standard. Breaking capacity is 10 kA Icu at 240 V AC phase-to-neutral (EN/IEC 60947-2), with a service breaking capacity Ics of 7.5 kA (75 %) at the same voltage — meaning it can safely clear a fault up to that level and still be reused after the event. Rated operational voltage is 240 V AC, single-pole switching, and the device is marked as suitable for isolation (EN/IEC 60947-2) — a required property when the MCB is used as a local disconnect.

Snaps onto 35 mm symmetrical DIN rail. Depth is 73 mm, height 81 mm. Terminals are tunnel type, accepting 1…25 mm² rigid or flexible (with or without ferrule). IP20 finger protection, so it's suited for enclosed distribution boards only — not for wet or dust-laden environments without an outer cabinet.

Meets EN/IEC 60947-2 as a Category A circuit breaker. Earth-leakage protection requires a separate block.

Frequently asked questions

How do I get current pricing and availability for MGN60506?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time against independent distribution channels.

What is the closest alternative to MGN60506 in the Multi9 family?

Within the same C60N series, a peer with a different curve or current rating (e.g., a 1 A curve C or a 2 A curve D) shares the same footprint and DIN-rail mounting, but the trip characteristics differ. No pin-compatible single alternative exists; the selection depends on your load's inrush profile.

What compliance documentation is available for MGN60506?

The breaker carries EN/IEC 60947-2 certification. Documentation such as the declaration of conformity is available from the manufacturer; contact your sourcing desk for specific RoHS/REACH declarations.

MPN
MGN60506