Schneider Electric MGN61866

Schneider Electric MGN61866 Multi9 C60H-DC MCB, 1P, 13 A, Cu

MPN MGN61866
Obsolete

Schneider Electric Multi9 C60H-DC, miniature circuit breaker, 1P, 13 A, curve K, 20 kA Icu at 110 V DC, clip-on DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN61866 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage250 V DC 110 V DC 220 V DC
Insulation voltage ui500 V DC conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN 60947-2

All specifications

MGN61866 additional specifications
ParameterValue
ColorGrey
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles3000 cycles L/R = 2 ms
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric MGN61866 is a Multi9 C60H-DC miniature circuit breaker, single-pole, rated 13 A at 50 °C with a K-curve magnetic trip at 12 x In. It is built for DC networks up to 250 V DC and clips onto a DIN rail — standard panel integration for distribution boards and control cabinets.

Rated at 20 kA Icu at 110 V DC and 10 kA Icu at 220 V DC per EN/IEC 60947-2, this breaker can safely interrupt a fault up to those levels without welding contacts or cascading upstream. On a 110 V DC bus — common in telecom and industrial control — the 20 kA rating covers most battery-backed supplies. At 220 V DC the 10 kA figure still handles substantial fault currents from solar strings or UPS banks.

Strip 14 mm and torque to 2.5 N.m. IP20 finger-safe with the modular enclosure; IP40 when installed in a panel.

K-curve trip characteristic

The K curve trips magnetically at 12 x In (156 A for this 13 A unit), ±20 %. This is designed for DC loads with moderate inrush — think contactor coils, solenoids, or DC motor drives — where a B curve would nuisance-trip but a Z curve would be too slow. Thermal-magnetic trip unit handles the overload side.

MPN