Skip to main content
Schneider Electric A9C61310

Schneider Electric A9C61310 Reflex iC60N, 10 A 3P Curve B, 2

MPN A9C61310
Obsolete

Schneider Electric Acti9 Reflex iC60N, integrated control circuit breaker, 10 A, 3P, curve B, 20 kA breaking capacity at 240 V AC, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9C61310 specifications
ParameterValue
Trip unit typeThermal-magnetic
Main product or component typeIntegrated control circuit breaker
Coil voltage230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC
Insulation voltage ui500 V AC
Breaking capacity20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
IP ratingIP20
Pollution degree3
ColorWhite
Depth77 mm
Width99 mm
Height84 mm
Electrical life cyclesAC-1: 50000 cycles AC 50 Hz
Mechanical life cycles50000 cycles
ApplicationControl Distribution

Product details

Breaking capacity is 20 kA Icu at 220–240 V AC and 10 kA at 380–415 V AC per EN/IEC 60947-2, which certifies it for industrial panel fault levels up to that range without upstream cascading. Three poles protected (3P), so it switches and protects all three phases simultaneously. Control voltage options span 24 V AC, 48 V AC, 230 V AC, 24 V DC, and 48 V DC — the 24 V DC variant is common for PLC or safety relay outputs; the 230 V AC version suits direct line-voltage control. The control type accepts maintained, impulse, or toggle signals, which gives flexibility for different remote-switching schemes. IP20 finger-safe terminals; separate earth-leakage block can be added downstream. Padlockable in the OFF position for LOTO compliance.

Where this class is used and deployment context

This is an integrated control circuit breaker — a single device that replaces a separate contactor + MCB pair in control and distribution panels. It is used where you need both remote on/off switching and overcurrent protection for a load: lighting circuits, small motor starters, resistive heating banks, or general distribution sub-circuits. The Reflex iC60N series sits in the Acti9 range, which is Schneider's modular DIN-rail platform for commercial and industrial panel building. The 10 A rating with B curve makes it suited for loads with low inrush — think lighting contactor duty or control transformer primary protection. For motor starting (higher inrush), a C or D curve would be more appropriate; this B curve will trip faster on inductive starts.

MPN