Skip to main content
Schneider Electric ATV6A0C40Q4

Schneider ATV6A0C40Q4 Altivar Process Drive, 400 kW ND

MPN ATV6A0C40Q4
Active

Schneider Electric Altivar Process ATV600, modular variable speed drive, ATV6A0C40Q4, 400 kW normal duty / 315 kW heavy duty at 400 V, integrated EMC filter C3, STO SIL 3, option card slots for fieldbus.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6A0C40Q4 specifications
ParameterValue
Main product or component typeVariable speed drive
Current681.0 A at 400 V (normal duty) 545.0 A at 400 V (heavy duty)
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.1 °C
Storage temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1

Product details

The Schneider Altivar Process ATV6A0C40Q4 is a modular variable speed drive rated for 400 kW normal duty and 315 kW heavy duty at 400 V three-phase, drawing 681 A line current in ND and 545 A in HD. The integrated EMC filter meets IEC 61800-3 category C3 with up to 300 m of motor cable, saving an external filter. Safety function STO (Safe Torque Off) is built in at SIL 3, eliminating the need for a separate safety relay for torque-off on the motor. Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (daisy chain RJ45, SUB-D 9, or screw terminals). Slot A and slot B also accept digital/analog I/O extension or output relay extension modules, giving flexibility for application-specific I/O without a separate remote rack.

Power and Ratings

Apparent power is 472 kVA at 400 V normal duty and 378 kVA at 400 V heavy duty. Output voltage is limited to the supply voltage (no boost), and the drive covers 50-60 Hz supply with ±5% tolerance. For installations above 1000 m altitude, derate current by 1% per 100 m up to 4800 m. Line supply harmonics: maximum THDI is <48% full load per IEC 61000-3-12, reducing the need for external line reactors in many applications. Pollution degree 2 per IEC 61800-5-1, suitable for typical control panel environments.

Communications and Control

Embedded Ethernet/Modbus TCP slave with half/full duplex and auto-negotiation at 10/100 Mbit/s. Modbus serial on 2-wire RS-485 at 4.8-38.4 kbit/s, RTU format, with configurable parity. The option slot expands to other fieldbuses as listed. Analog input accuracy: ±0.6% over 60°C temperature variation; linearity error ±0.15% of max value. Analog output accuracy ±1% over 60°C; linearity ±0.2%. Sampling times: discrete inputs 2 ms/5 ms, analog inputs 5 ms, analog output 10 ms. Relay outputs refresh within 5 ms (±0.5 ms).

Standards compliance includes IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental), IEC 61508 and IEC 13849-1 (functional safety). CE marked.

Mounting and Environmental

Cabinet mount only, forced convection cooling. Rated for operating temperature 0-50°C (no derating quoted), relative humidity 5-95% non-condensing per IEC 60068-2-3. Shock resistance 7 g for 11 ms per IEC 60068-2-27.

MPN