The control circuit runs on 230 V AC at 50 Hz, drawing 11 VA inrush and holding at 1.1 VA. The relay is rated for 5 million cycles under AC-21 and AC-22 duty (resistive and mixed resistive-inductive loads), so it's a fit for frequent switching applications like corridor or stairwell lighting where you want the contactor to stay latched without coil power draw between pulses.
Neutral is on the left. Terminals accept up to 4 mm² rigid or 2.5 mm² flexible cable, with a tunnel-type connection top and bottom. Strip length is 10 mm; tighten to 1 N·m. IP20 on the opening (finger-safe when wired), IP40 inside an enclosure. The tropicalisation treatment (class 2 per IEC 60068-1) handles humidity up to 95% at 55 °C, so it's fine for non-condensing environments like plant floors or enclosed switchboards.