Skip to main content
Schneider Electric A9C15183 — Contactors

A9C15183 Acti9 CT Contactor, 2P, 25 A, 230 V AC

MPNA9C15183
Obsolete

Schneider Electric Acti9 CT contactor, A9C15183, 2P, 25 A AC-7A rated operational current, 230 V AC 50 Hz control voltage, clip-on DIN rail mount, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9C15183 — Identification
ParameterValue
Product / component typeContactor
A9C15183 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)250 V AC 50 Hz
Utilisation categoryAC-1 conforming to IEC 60947-4
A9C15183 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Operating altitude2000 m
A9C15183 — Approvals
ParameterValue
StandardsIEC 61095 EN 61095
A9C15183 — Mechanical
ParameterValue
Width18 mm
Height90 mm
Depth66 mm

Product details

Acti9 CT Contactor – A9C15183

It clips onto a 35 mm symmetrical DIN rail and occupies 2 x 9 mm pitches (18 mm wide), so it fits neatly into a compact modular enclosure alongside other Acti9 devices. Rated operational current is 25 A in AC-7A category and 8.5 A in AC-7B — the AC-7A figure governs resistive loads like lighting or heating, while AC-7B covers inductive loads typical of small motors. Control voltage is 230 V AC at 50 Hz, with an inrush of 15 VA and a hold-in draw of 3.8 VA.

For motor loads, the AC-7B rating of 8.5 A is the figure to use — that's the inductive switching capacity. The 230 V AC control coil is standard for European panel builds, and the 50/60 Hz tolerance means it works on both common mains frequencies. Pollution degree 2 is the typical industrial environment where only non-conductive pollution occurs, with occasional condensation.

The 18 mm width (2 x 9 mm pitches) matches the Acti9 modular system, so it aligns with MCBs, RCDs, and other Acti9 devices on the same rail. Power circuit terminals are tunnel type: accept up to 2 x 2.5 mm² flexible or 1 x 6 mm² rigid. Control circuit terminals take 2 x 2.5 mm² flexible or 2 x 1.5 mm² rigid. Wire stripping length is 10 mm, tightening torque 0.8 N·m. The 2 NO pole contact composition gives two normally-open main contacts.

Frequently asked questions

What are the key ratings for the A9C15183?

Rated operational current is 25 A in AC-7A (resistive loads) and 8.5 A in AC-7B (inductive motor loads). Control voltage is 230 V AC at 50 Hz. Rated operational voltage is 250 V AC. Maximum power is 3 W at 250 V AC.

What standards does the A9C15183 comply with?

It complies with IEC 61095 and EN 61095 for electromechanical contactors for household and similar purposes. Utilisation category AC-1 per IEC 60947-4 is also listed.

What is the physical size and mounting of the A9C15183?

Dimensions are 90 mm height, 18 mm width (2 x 9 mm pitches), 66 mm depth. It clips onto a 35 mm symmetrical DIN rail. IP20 rated on the body, IP40 inside a modular enclosure.

MPN