Skip to main content
Schneider Electric A9C15186 — Contactors

Schneider Electric A9C15186 Acti9 CT Contactor, 2P, 25 A, 23

MPNA9C15186
Obsolete

Schneider Electric Acti9 CT contactor, A9C15186, 2P, 25 A AC-7A, 230 V AC 50 Hz control, clip-on 35 mm DIN rail, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9C15186 — Identification
ParameterValue
Product / component typeContactor
A9C15186 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)250 V AC 50 Hz
Utilisation categoryAC-1 conforming to IEC 60947-4
A9C15186 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Operating altitude2000 m
A9C15186 — Approvals
ParameterValue
StandardsIEC 61095 EN 61095
A9C15186 — Mechanical
ParameterValue
Width18 mm
Height90 mm
Depth66 mm

Product details

Rated operational current is 25 A in AC-7A category (general-use resistive and inductive loads up to 250 V AC) and 8.5 A in AC-7B category (motor loads). The control coil is 230 V AC at 50 Hz, drawing 15 VA inrush and 3.8 VA hold-in. That means the coil's steady-state draw is low enough to daisy-chain multiple contactors on a single PLC output without exceeding the output's current rating. The contactor is certified to IEC 61095 and EN 61095 — the standards for electromechanical contactors for household and similar purposes — and carries an AC-1 utilisation category per IEC 60947-4 for non-inductive or slightly inductive loads.

Integration notes

The 18 mm width means it takes one standard modular pitch. Terminals are tunnel type: power circuit accepts up to 2 x 2.5 mm² flexible or 1 x 6 mm² rigid; control circuit accepts 2 x 2.5 mm² flexible or 2 x 1.5 mm² rigid. Wire stripping length is 10 mm; tightening torque is 0.8 N·m. IP20 body protection (IP40 in modular enclosure) means it is suited for dry indoor panels only — not for washdown or outdoor locations. The contactor is remotely and manually controlled with a maintained control signal. Local signalling is via a colour indicator. Switching frequency is rated at 100 operations per day — fine for on/off control of lighting, HVAC contactors, or small motor starters, but not for high-cycling applications like rapid conveyor indexing.

Frequently asked questions

What are the key ratings for A9C15186?

Rated operational current is 25 A AC-7A / 8.5 A AC-7B at 250 V AC. Control coil is 230 V AC 50 Hz. It is a 2-pole, normally-open contactor.

What compliance standards does A9C15186 meet?

It is certified to IEC 61095 and EN 61095, and carries an AC-1 utilisation category per IEC 60947-4. Pollution degree 2 and IP20/IP40 protection.

MPN
A9C15186