Schneider Electric A9C52340 — Contactors

A9C52340 Reflex iC60N 40A 3P C-curve MCB, 20kA

MPNA9C52340
Obsolete

Schneider Electric Acti9 Reflex iC60N integrated control circuit breaker, 40 A, 3P, curve C, 20 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9C52340 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C52340 — Contacts & Poles
ParameterValue
Pole configuration3P
A9C52340 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C52340 — Mechanical
ParameterValue
Width99 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C52340 is a Reflex iC60N integrated control circuit breaker from the Acti9 range — a 3-pole, 40 A thermal-magnetic MCB with a C-curve trip characteristic, designed for control and distribution applications on AC networks at 50/60 Hz. It mounts on a 35 mm symmetrical DIN rail, fixed position, and occupies 11 x 9 mm pitches (99 mm width) — standard panel footprint for a 3P device.

Control and signalling

The control circuit accepts multiple voltages: 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — so it works with both AC and DC control systems common in industrial panels. Control is by maintained or impulse signal, with a toggle ON/OFF button and remote pulse capability. Local signalling includes a green LED for ON, red for fault, flashing for trip or overheat — gives a quick visual on the panel door without opening the enclosure. A contact position indicator and padlock provision (OFF position) support lockout/tagout procedures.

Integration notes

IP20 rated per IEC 60529 — suitable for dry indoor enclosures only; not for washdown or outdoor use. Earth-leakage protection requires a separate block (not integrated), so plan for an external RCCB or RCBO if ground-fault protection is needed. Electrical durability is 50,000 cycles at AC-1 (resistive load) — fine for frequent switching in lighting or distribution panels. Mechanical durability matches at 50,000 cycles.

Frequently asked questions

What is the breaking capacity of this MCB?

20 kA Icu at 220...240 V AC and 10 kA Icu at 380...415 V AC, both conforming to EN/IEC 60947-2. The N breaking capacity code indicates the standard interrupting rating for the Reflex iC60N series.

What control voltages does it accept?

The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — all at 50/60 Hz for AC versions. Control can be maintained or impulse signal.

Does it include earth-leakage protection?

No, earth-leakage protection requires a separate block. The A9C52340 is a thermal-magnetic MCB only, not an RCBO.

MPN
A9C52340