Schneider Electric A9C52416 — Contactors

Schneider Electric A9C52416 Reflex iC60N MCB, 16 A, 4P, C Cu

MPNA9C52416
Obsolete

Schneider Electric Acti9 Reflex iC60N integrated control circuit breaker, A9C52416, 16 A rated, 4 poles, curve C, 20 kA breaking capacity at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9C52416 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C52416 — Contacts & Poles
ParameterValue
Pole configuration4P
A9C52416 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C52416 — Mechanical
ParameterValue
Width117 mm
Height84 mm
Depth77 mm

Product details

The Schneider Electric A9C52416 is a Reflex iC60N integrated control circuit breaker from the Acti9 range, combining overcurrent protection with remote switching capability in a single 4-pole unit rated at 16 A with a C trip curve. Breaking capacity is 20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, certified to EN/IEC 60947-2 — sufficient for most commercial and light industrial distribution panels where fault levels stay under those thresholds.

Control and signalling

Control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC, with both maintained and impulse control signal types — so it works with a standard pushbutton, a PLC digital output, or a remote switch without an interposing relay. Local signalling includes a green LED for device ON, a flashing LED for device ready, tripped, or overheat conditions, plus a red LED for fault — enough status feedback to troubleshoot without opening the panel door. The toggle ON/OFF button on the front allows manual override, and the padlockable OFF position secures isolation for maintenance lockout.

Depth is 77 mm, height 84 mm, IP20 finger-safe terminals — standard for enclosure mounting with a transparent door or cover.

The Reflex iC60N integrates a control relay and an MCB into one package, which simplifies panel wiring and reduces component count compared to separate contactor and breaker combinations — a genuine space and labour saving if the 16 A rating fits your load.

Frequently asked questions

What control voltages does the A9C52416 accept?

The control circuit accepts 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC, with both maintained and impulse signal types.

What is the breaking capacity of the A9C52416?

Breaking capacity is 20 kA Icu at 220–240 V AC and 10 kA Icu at 380–415 V AC, certified to EN/IEC 60947-2.

Does the A9C52416 include earth-leakage protection?

No, earth-leakage protection requires a separate block — it is not built into this unit.

What is the electrical durability of the A9C52416?

Electrical durability is 50,000 cycles under AC-1 resistive load at 50 Hz; mechanical durability is also 50,000 cycles.

MPN