Skip to main content
Schneider Electric A9C62325 — Contactors

Schneider Electric A9C62325 Reflex iC60N, 25 A 3P C-curve, i

MPNA9C62325
Obsolete

Schneider Electric Acti9 Reflex iC60N, integrated control circuit breaker, 25 A, 3P, curve C, thermal-magnetic trip, 20 kA Icu at 230 V AC.

$429.95Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9C62325 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C62325 — Contacts & Poles
ParameterValue
Pole configuration3P
A9C62325 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C62325 — Mechanical
ParameterValue
Width99 mm
Height84 mm
Depth77 mm

Product details

It combines overcurrent protection (thermal-magnetic trip, curve C) with local and remote switching control in a single DIN-rail module. Rated 25 A on a 3-pole (3P) network at 230 V AC, 50/60 Hz, it serves distribution and control applications where you need both a circuit breaker and a contactor in one package. The breaking capacity is 20 kA Icu at 220…240 V AC and 10 kA Icu at 380…415 V AC, per EN/IEC 60947-2.

Control and signalling

Control is via ON/OFF button, remote pulse, remote continuous command, or toggle — the control circuit accepts 24 V AC/DC, 48 V AC/DC, or 230 V AC. Local signalling includes a green LED for device ON, flashing red for tripped, and flashing for overheat or device ready. This makes fault isolation straightforward for field service: a quick visual check tells you whether the unit is healthy, tripped on overload, or thermally stressed.

Dimensions are 99 mm wide (11 x 9 mm pitches), 84 mm high, 77 mm deep. IP20 finger-safe terminals per IEC 60529; the device is padlockable in the OFF position. For a panel OEM wiring this into a control cabinet, the 77 mm depth leaves clearance under a standard 120 mm deep enclosure gland plate — no need to oversize the box.

Pollution degree 3 (industrial environment with conductive or dry non-conductive pollution). Tropicalisation class 2. Relative humidity tolerance of 93 % at 40 °C. The device accepts separate earth-leakage protection block. These specs support qualification for controlled environments: the thermal-magnetic trip curve is fixed, no firmware auto-update, so the protection profile is stable under change control.

Frequently asked questions

What is the breaking capacity of the A9C62325?

20 kA Icu at 220…240 V AC and 10 kA Icu at 380…415 V AC, per EN/IEC 60947-2.

What control voltages does the A9C62325 accept?

The control circuit accepts 24 V AC/DC, 48 V AC/DC, or 230 V AC at 50/60 Hz.

What is the physical size of the A9C62325?

99 mm wide (11 x 9 mm pitches), 84 mm high, 77 mm deep. Mounts on 35 mm DIN rail.

MPN
A9C62325