Skip to main content
Schneider Electric A9C64416 — Contactors

Schneider Electric A9C64416 Reflex iC60H Ti24 16A 4P Curve B

MPNA9C64416
Obsolete

Schneider Electric Acti9 Reflex iC60H Ti24, A9C64416, integrated control MCB, 16 A, 4P, curve B, 30 kA Icu at 230 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9C64416 — Identification
ParameterValue
Product / component typeIntegrated control circuit breaker
Series / rangeActi9
A9C64416 — Contacts & Poles
ParameterValue
Pole configuration4P
A9C64416 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
A9C64416 — Mechanical
ParameterValue
Width117 mm
Height84 mm
Depth77 mm

Product details

Integrated control circuit breaker for panel-based distribution

The Schneider Electric A9C64416 is a Reflex iC60H Ti24 integrated control circuit breaker from the Acti9 range, combining overcurrent protection with local and remote switching in a single 4-pole unit. Rated 16 A with a B curve, it is designed for control distribution panels where you need both a disconnecting means and motor/load switching under one DIN-rail footprint.

The 30 kA Icu at 230 V AC (15 kA at 415 V AC) per EN/IEC 60947-2 tells you this breaker can interrupt a fault up to that level without welding its contacts — critical for panel SCCR coordination. Control voltage options span 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC, with three control signal types (maintained very low voltage, impulse, maintained). This means the same part works with a PLC digital output (24 V DC impulse) or a panel pushbutton (230 V AC maintained) — no separate contactor needed for the switching function.

Integrated control circuit breakers like the Reflex iC60 are used in control distribution panels to combine branch circuit protection with local on/off switching and remote control via a pulse or maintained signal. Typical applications include HVAC control panels, lighting contactor replacement, pump control, and small machine control where a separate contactor and breaker would take up twice the DIN-rail space.

Frequently asked questions

What are the key ratings for the A9C64416?

Rated current 16 A, 4 poles, curve B, breaking capacity 30 kA Icu at 230 V AC and 15 kA at 415 V AC per EN/IEC 60947-2. Control voltage options include 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC. Rated insulation voltage is 500 V AC.

MPN
A9C64416