Rated at 25 A with a D curve, it handles high inrush loads typical of motor and transformer circuits without nuisance tripping, while the 4-pole configuration (4P) switches all phases and neutral. Breaking capacity is 30 kA Icu at 220…240 V AC and 15 kA Icu at 380…415 V AC, both per EN/IEC 60947-2 — sufficient for most commercial and light industrial panelboards where fault levels stay below those thresholds.
Control and integration
The control circuit accepts multiple voltage options — 230 V AC, 24 V AC, 48 V AC, 24 V DC, or 48 V DC — and supports maintained, impulse, or maintained very-low-voltage signals, so it adapts to both building-management and PLC-driven schemes. Local signalling includes a green LED for ON status, a flashing LED for tripped or overheat conditions, and a red LED for fault — enough diagnostic feedback to clear a line-down event without opening the panel door.
Earth-leakage protection is handled by a separate block (not integrated), so the same breaker can be paired with a Vigi iC60 module when ground-fault detection is required. Rated insulation voltage is 500 V AC, pollution degree 3, and tropicalisation class 2 — suitable for non-condensing environments up to 93 % relative humidity at 40 °C.