The Schneider Electric A9D60606 is an Acti9 iDPN Vigi RCBO — a combined miniature circuit breaker and residual-current device in a single 36 mm wide module, 1P+N configuration, rated 6 A with a B-curve trip characteristic and 100 mA earth-leakage sensitivity.
The 6 A rated current (In) and B-curve (magnetic trip at 3 to 5 times In) mean this RCBO is sized for lighting circuits, small appliance loads, or control transformers — not motor or high-inrush loads. The 6 kA breaking capacity (Icn at 230–240 V AC, 50 Hz, per EN/IEC 61009-2-1) is the standard domestic-commercial fault-interrupting rating; it safely clears a short-circuit up to 6 kA without welding the contacts or cascading damage upstream. The 100 mA earth-leakage threshold provides personnel and equipment protection against ground faults, not the 30 mA level used for direct human contact protection — so it suits submain or distribution circuits where a lower sensitivity would cause nuisance tripping. Thermal-magnetic trip technology gives the bimetal overload curve for sustained overcurrents and the solenoid for short-circuit response.
Neutral is on the left, phase on the right — check your busbar orientation before wiring. Terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible, with a 15 mm strip length and 2 Nm tightening torque. The 9 mm pitch between phase and neutral terminals is the standard for modular RCBOs in this form factor.