Skip to main content
Schneider Electric A9D60606 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D60606 Acti9 iDPN Vigi, 6A B-curve RCBO

MPNA9D60606
Obsolete

Schneider Electric Acti9 iDPN Vigi RCBO, A9D60606, 6 A rated, B-curve, 6 kA breaking capacity, 100 mA earth leakage, 1P+N, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D60606 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D60606 — Electrical Ratings
ParameterValue
Rated current (In)6 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D60606 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPN N Vigi
A9D60606 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D60606 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D60606 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9D60606 is an Acti9 iDPN Vigi RCBO — a combined miniature circuit breaker and residual-current device in a single 36 mm wide module, 1P+N configuration, rated 6 A with a B-curve trip characteristic and 100 mA earth-leakage sensitivity.

The 6 A rated current (In) and B-curve (magnetic trip at 3 to 5 times In) mean this RCBO is sized for lighting circuits, small appliance loads, or control transformers — not motor or high-inrush loads. The 6 kA breaking capacity (Icn at 230–240 V AC, 50 Hz, per EN/IEC 61009-2-1) is the standard domestic-commercial fault-interrupting rating; it safely clears a short-circuit up to 6 kA without welding the contacts or cascading damage upstream. The 100 mA earth-leakage threshold provides personnel and equipment protection against ground faults, not the 30 mA level used for direct human contact protection — so it suits submain or distribution circuits where a lower sensitivity would cause nuisance tripping. Thermal-magnetic trip technology gives the bimetal overload curve for sustained overcurrents and the solenoid for short-circuit response.

Neutral is on the left, phase on the right — check your busbar orientation before wiring. Terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible, with a 15 mm strip length and 2 Nm tightening torque. The 9 mm pitch between phase and neutral terminals is the standard for modular RCBOs in this form factor.

Frequently asked questions

Where can I buy the A9D60606 and get a price?

The A9D60606 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock or price figures are published here.

What is the breaking capacity of the A9D60606?

The A9D60606 has a breaking capacity of 6000 A Icn at 230–240 V AC, 50 Hz, conforming to EN/IEC 61009-2-1.

What earth-leakage sensitivity does the A9D60606 provide?

The integrated earth-leakage protection is set at 100 mA sensitivity — suitable for submain or distribution circuits where 30 mA would cause nuisance tripping.

What compliance documentation does Schneider provide for the A9D60606?

The A9D60606 is certified to EN/IEC 61009-2-1, carries overvoltage category III per IEC 60364, pollution degree 3, and tropicalisation class 2 per IEC 60068-1. The manufacturer provides the standard declaration of conformity and product certificate — request these with your RFQ.

MPN