Skip to main content
Schneider Electric A9D87420 — Residual Current Breakers (RCCB/RCBO)

A9D87420 Acti9 iC60 RCBO, 4P, 20 A, 30 mA, Curve B, 6 kA

MPNA9D87420
Active

Schneider Electric Acti9 iC60 RCBO, 4P, 20 A, 30 mA, curve B, 6 kA, 4 protected poles, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D87420 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D87420 — Electrical Ratings
ParameterValue
Rated current (In)20 A
Rated operational voltage (Ue)380...415 V AC 50 Hz
Poles description4P
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)500 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D87420 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60 RCBO
A9D87420 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsTunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Terminal tightening torque2 N.m
Width72 mm
Height86 mm
Depth78 mm
A9D87420 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D87420 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 61009-2-1

Product details

The A9D87420 is a 4-pole Acti9 iC60 RCBO — a combined miniature circuit breaker and residual-current device in one 72 mm wide DIN-rail module. It protects a 4-wire outgoing circuit against overload, short-circuit (curve B, 3 to 5 times In magnetic trip), and earth leakage at 30 mA sensitivity. The 6 kA breaking capacity at 380–415 V AC meets EN/IEC 60947-2 and EN/IEC 61009-2-1, so it's rated for distribution boards in commercial and light industrial panels where the prospective fault current stays under that level.

Rated 20 A with a thermal-magnetic trip unit — the thermal element handles sustained overloads, the magnetic element clears short-circuits above 60 A (3–5 × In). The 30 mA residual-current sensitivity is the standard for personnel protection in most IEC 60364 installations; it trips on leakage to earth, not on line-to-neutral faults. That's adequate for most sub-distribution boards fed by a transformer or a main breaker with a lower let-through. Limitation class 1 per EN/IEC 61009-2-1 means it lets through the full prospective current during a short-circuit — it does not current-limit like a higher-class MCB. That matters for downstream equipment with limited short-circuit withstand; you'd coordinate it with an upstream current-limiting device if the load is sensitive.

Clip-on mount to standard 35 mm DIN rail. The 72 mm width (8 × 9 mm pitches) means it occupies four 18 mm modular spaces — plan your rail fill accordingly. The 9 mm pole-to-pole pitch matches the Acti9 busbar system, so you can feed it with a pre-wired distribution bar without individual ring-tongue terminations. IP40 in the distribution enclosure keeps dust out; IP20 on the terminals is standard for touch-safe finger protection.

The Acti9 iC60 series is a broad, widely stocked platform, so this 4P 20 A 30 mA variant is a standard catalogue item.

Frequently asked questions

What is the breaking capacity of A9D87420?

6 kA Icn and 6 kA Icu at 380–415 V AC, 50 Hz, conforming to EN/IEC 61009-2-1 and EN/IEC 60947-2.

What earth leakage sensitivity does this RCBO have?

30 mA, integrated into the same module as the overcurrent protection.

Where can I buy A9D87420 and get current pricing?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

MPN
A9D87420