Schneider Electric A9DG2616 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9DG2616 Acti9 iCV40 RCBO, 16A, 30mA, B-C

MPNA9DG2616
Active

Schneider Electric Acti9 iCV40 RCBO, 1P+N, 16 A, 30 mA, B-curve, 4500 A, DIN rail.

$168.53Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9DG2616 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication
A9DG2616 — Electrical Ratings
ParameterValue
Rated current (In)16 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9DG2616 — Identification
ParameterValue
Product nameActi9 iCV40
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiCV40
A9DG2616 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminals top or bottom 1...16 mm² rigid Tunnel type terminals top or bottom 1...10 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9DG2616 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Operating altitude2000 m
A9DG2616 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9DG2616 is an Acti9 iCV40 RCBO — a combined residual-current circuit breaker with overcurrent protection in a single 36 mm-wide, 1P+N module. Breaking capacity is 4500 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1.

The 16 A rated current (In) sets the continuous load limit for the outgoing circuit — size your downstream conductors and loads to stay under this. The 30 mA earth-leakage threshold provides personal protection against direct contact; it is the standard sensitivity for socket-outlet circuits in many domestic and commercial installations. The B-curve (3–5 x In magnetic trip) means the breaker will hold through mild motor inrush or capacitive loads but trips quickly on a hard short — a good match for lighting, small appliances, and general-purpose outlets where the load profile is predictable. In a distribution board, this limits where the RCBO can be placed downstream of a larger upstream breaker or fuse that clips the prospective fault current below 4.5 kA. Thermal-magnetic trip technology means the thermal element handles sustained overloads (slow, heat-dependent) while the magnetic coil reacts to short-circuit currents. The 20000-cycle electrical and mechanical endurance is typical for this class of RCBO — adequate for normal switching duty in a distribution board, but not intended for frequent load-break applications like motor starting.

Tunnel-type terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip 14 mm and tighten to 2 N·m.

Frequently asked questions

Where can I buy the A9DG2616 and get a price?

The A9DG2616 is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current availability and pricing — stock levels and lead times are confirmed at quote time.

What are the key ratings of the A9DG2616?

The A9DG2616 is a 16 A, 30 mA, B-curve RCBO with a 4500 A breaking capacity at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. It is a 1P+N module, 36 mm wide, for DIN-rail mounting.

What compliance documentation does Schneider provide for the A9DG2616?

The A9DG2616 carries KEMA-KEUR and VDE quality labels and conforms to EN/IEC 61009-2-1. It is rated for pollution degree 3 and overvoltage category III per IEC 60364. The manufacturer typically provides a Declaration of Conformity and product-specific compliance certificates upon request.

MPN
A9DG2616