Skip to main content
Schneider Electric A9F03232 — 2-Pole MCB (DIN Rail)

Schneider Electric A9F03232 Acti9 iC60N MCB, 32 A, 2P, Curve

MPNA9F03232
Active

Schneider Electric Acti9 iC60N, A9F03232, miniature circuit-breaker, 32 A, 2-pole, curve B, 36 kA Icu at 12-133 V AC, DIN rail mount, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F03232 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameIC60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F03232 — Electrical
ParameterValue
Rated current [In]32 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)DC AC
Network frequency50/60 Hz
A9F03232 — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity (Icu)36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F03232 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F03232 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F03232 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

Miniature circuit-breaker, 32 A, 2-pole, curve B

The Schneider Electric A9F03232 is an Acti9 iC60N miniature circuit-breaker rated 32 A with 2 protected poles and a B tripping curve (4 x In magnetic trip, ±20 %). It carries a 36 kA Icu breaking capacity at 12–133 V AC and 20 kA Icu at 220–240 V AC, both per EN/IEC 60947-2, plus a 10 kA Icn at 400 V AC per EN/IEC 60898-1. That dual-standard rating means it can serve as a branch-circuit protective device under 60947-2 for industrial panels or as a final-subcircuit MCB under 60898-1 for distribution boards — same part, different passport. The thermal-magnetic trip unit handles overloads and short-circuits. Overvoltage category IV and pollution degree 3 ratings confirm it is designed for main panel installation, not downstream subpanels.

The double terminal accepts 1–35 mm² rigid or 1–25 mm² flexible on top or bottom; strip length is 14 mm. A visible trip indicator and contact position indicator give local status without needing to remove the cover. The toggle control is manual on-off, with a separate earth-leakage block available as an add-on (not integrated).

This is a standard catalogue item from Schneider Electric's Acti9 range. For volume or scheduled releases, a blanket PO with release dates typically secures better lead-time consistency.

Frequently asked questions

What is the breaking capacity of the A9F03232?

36 kA Icu at 12–133 V AC, 20 kA Icu at 220–240 V AC, 10 kA Icu at 380–415 V AC, and 6 kA Icu at 440 V AC, all per EN/IEC 60947-2. It also carries a 10 kA Icn at 400 V AC per EN/IEC 60898-1.

What is the closest alternative to the A9F03232 in the same family?

Within the Acti9 iC60N range, the same physical footprint and terminal layout is shared across all current ratings and pole configurations. The deciding factor is the rated current (32 A) and curve B — a 40 A or curve C variant would be a different order code but mechanically interchangeable.

Where can I buy the A9F03232 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock figures are published here.

What compliance documentation does Schneider provide for the A9F03232?

The part is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries tropicalisation class 2 per IEC 60068-1. RoHS and REACH declarations are standard for the Acti9 range; specific declaration documents are available on request.

MPN