Skip to main content
Schneider Electric A9F03610 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F03610 Acti9 iC60N MCB, 10 A, 1P+N, B C

MPNA9F03610
Active

Schneider Electric Acti9 iC60N, A9F03610, miniature circuit breaker, 1P+N, 10 A, B-curve, 36 kA breaking capacity at 12-60 VAC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F03610 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9F03610 — Electrical & Protection
ParameterValue
Rated current (In)10 A
Tripping curve codeB
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F03610 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width36 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9F03610 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F03610 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F03610 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F03610 is an Acti9 iC60N miniature circuit breaker — 1P+N, 10 A rated, B-curve, thermal-magnetic trip. It's a current-production distribution breaker (lifecycle stage: current) built for DIN-rail panels where you need a switched neutral and a single protected pole.

This breaker carries a 36 kA Icu at 12-60 V AC (EN/IEC 60947-2), 20 kA at 100-133 V, and 10 kA at 220-240 V. Under the residential-standard EN/IEC 60898-1 it's rated 6000 A Icn at 230 V. The dual-standard rating (60947-2 for industrial, 60898-1 for domestic) gives you flexibility in specification: you can use it in a distribution board or an industrial sub-panel.

Trip curve and coordination

B-curve means magnetic trip at 4 x In (40 A, +/-20%). For motor or drive circuits you'd typically step to C or D curve, but for distribution duty this holds selectivity well with upstream C-curve breakers. The thermal-magnetic trip unit gives you inverse-time overload protection (thermal) plus instantaneous short-circuit (magnetic).

Height is 91 mm, depth 78.5 mm — check your gland plate clearance if you're fitting a deep enclosure. Terminals accept 1-25 mm² rigid or 1-16 mm² flexible, double-terminal top and bottom for daisy-chaining. IP20 finger-safe, pollution degree 3 (conductive pollution environment — typical for industrial panels not sealed from the floor).

Frequently asked questions

Who supplies A9F03610 and how is it quoted for volume purchases?

We source the A9F03610 through our independent distribution network and quote it to order against an RFQ. Availability and current pricing are confirmed at quote time — send the quantity and target delivery window.

What is the closest pin-compatible alternative to A9F03610 in this component family?

Within the Acti9 iC60N family, the closest alternative would be a different current rating or curve code — same 1P+N form factor, same DIN-rail footprint, same terminal layout. For example, an A9F03610 swaps to a C-curve (A9F03620) or a 16 A B-curve (A9F03616) without changing the panel layout. No other manufacturer's breaker is pin-compatible; the iC60N terminal spacing and neutral position are proprietary to Schneider.

What compliance documentation does this brand provide for A9F03610?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries IP20 protection, pollution degree 3, overvoltage category IV, and tropicalisation class 2 per IEC 60068-1. Isolation suitability is confirmed under both standards. Standard documentation includes the declaration of conformity and the product datasheet; specific RoHS/REACH declarations are available from Schneider on request.

MPN