Skip to main content
Schneider Electric A9F04413 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F04413 Acti9 iC60N MCB, 13 A, 4P, C-Cur

MPNA9F04413
Active

Schneider Electric Acti9 iC60N, miniature circuit breaker, 4P, 13 A, C-curve, 36 kA breaking capacity, DIN rail, white.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F04413 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F04413 — Ratings
ParameterValue
Rated current (In)13 A
Poles configuration4P
Number of protected poles4
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F04413 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F04413 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F04413 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F04413 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F04413 is an Acti9 iC60N miniature circuit breaker rated at 13 A with 4 protected poles and a C-curve trip characteristic. It carries a 36 kA Icu breaking capacity at 12–133 V AC and 10 kA Icu at 380–415 V AC per EN/IEC 60947-2, plus a 6 kA Icn at 400 V AC per EN/IEC 60898-1. That dual-standard rating means it can serve both industrial panel distribution (60947-2) and final-circuit protection (60898-1) in the same enclosure — useful when a single breaker must satisfy both a machine builder's SCCR requirement and the local wiring code.

The 36 kA Icu at low voltage (12–133 V AC) is the headline number, but the figure that governs most 400 V panel designs is the 10 kA Icu at 380–415 V AC. That is the rating the upstream transformer and bus bracing must coordinate with. The C-curve magnetic trip is set at 8 x In ±20 %, so on a 13 A breaker the instantaneous trip starts around 83 A and is guaranteed by 125 A — fast enough to clear a bolted fault before the upstream device sees it, provided the let-through energy (limitation class 3 per EN/IEC 60898-1) stays within the downstream cable's withstand.

Frequently asked questions

Where can I buy A9F04413 and how do I get a price?

The A9F04413 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm landed-cost figure.

What is A9F04413's listed depth (78.5 mm) on this component line?

The depth is 78.5 mm, measured from the DIN-rail mounting face to the front of the toggle. Combined with the 72 mm width (4 module spaces) and 91 mm height, it fits standard distribution board cutouts.

What compliance documentation does this brand provide for A9F04413?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, which covers the IEC standards for industrial and household MCBs. Pollution degree 3 and overvoltage category IV are declared per those standards. Tropicalisation class 2 per IEC 60068-1 is also documented.

MPN
A9F04413