Skip to main content
Schneider Electric A9F04601 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F04601 Acti9 iC60N MCB, 1P+N, 1 A, C-Cu

MPNA9F04601
Active

Schneider Electric Acti9 iC60N, miniature circuit breaker, 1P+N, 1 A, C-curve, 50 kA breaking capacity, DIN rail mount, white.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F04601 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9F04601 — Electrical & Protection
ParameterValue
Rated current (In)1 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)50 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F04601 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width36 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9F04601 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F04601 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F04601 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F04601 is a 1 A miniature circuit breaker from the Acti9 iC60N series, built for distribution-level protection on DIN-rail panels. It's a 1P+N thermal-magnetic breaker with a C-curve — meaning it trips magnetically at 8 x In (±20 %), so it handles moderate inrush from small motor starters or lighting ballasts without nuisance tripping, but clears a hard short fast.

Breaking capacity and standards

Rated breaking capacity hits 50 kA Icu at 220–240 V AC per IEC 60947-2, and 6 kA Icn at 230 V per IEC 60898-1. That dual-rating means it's certified for both industrial (60947-2) and residential/commercial (60898-1) installations — a single part covers the panel builder's coordination study and the site's wiring rules.

Snaps onto standard DIN rail, occupies 4 x 9 mm pitches (36 mm wide). The neutral is on the left, fixed position; no swapping for reversed-phase panels.

Frequently asked questions

What is the breaking capacity of the A9F04601?

50 kA Icu at 220–240 V AC per IEC 60947-2, and 6 kA Icn at 230 V per IEC 60898-1.

What is the A9F04601 used for?

It's a 1 A miniature circuit breaker for distribution panels, protecting a single pole plus neutral circuit with a C-curve trip characteristic.

Where can I buy the A9F04601?

Sourced and quoted to order against an RFQ through independent distribution; current pricing and lead time are confirmed at quote time.

MPN
A9F04601