Skip to main content
Schneider Electric A9F05110 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F05110 Acti9 iC60N MCB, 10 A, D Curve,

MPNA9F05110
Active

Schneider Electric Acti9 iC60N, miniature circuit-breaker, 1P, 10 A, D curve, 36 kA Icu at 12…60 V AC, DIN rail mount, white.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F05110 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F05110 — Electrical & Protection
ParameterValue
Rated current (In)10 A
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F05110 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom

Environmental

A9F05110 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F05110 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F05110 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F05110 is an Acti9 iC60N miniature circuit breaker — a 1-pole, 10 A thermal-magnetic MCB with a D tripping curve. It's built for distribution duty in a 2-module (18 mm per pole) DIN-rail footprint, so it slots straight into a standard panel enclosure alongside other Acti9 kit.

Breaking capacity — what it means on the line

This breaker carries dual-standard ratings: 36 kA Icu at 12…60 V AC and 10 kA Icu at 220…240 V AC per IEC 60947-2, plus 6 kA Icn at 230 V AC per IEC 60898-1. The 36 kA figure covers low-voltage AC distribution where fault current can spike — think panel feeds close to a transformer. On the DC side, it's rated 15 kA Icu at 12…60 V DC and 10 kA at 60…72 V DC — useful for DC distribution in telecom shelters or control cabinets where battery-backed 48 V loops need short-circuit protection.

Snaps onto a DIN rail (35 mm symmetrical rail per EN 60715).

Frequently asked questions

What is the breaking capacity of A9F05110?

36 kA Icu at 12…60 V AC, 10 kA Icu at 220…240 V AC per IEC 60947-2, and 6 kA Icn at 230 V AC per IEC 60898-1. On DC, 15 kA Icu at 12…60 V DC.

What standards does A9F05110 comply with?

It complies with EN/IEC 60947-2 and EN/IEC 60898-1, and is suitable for isolation per both standards.

Where can I buy A9F05110 and get current pricing?

The A9F05110 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
A9F05110