Rated 2 A continuous, thermal-magnetic trip unit. The magnetic threshold at 12 x In (24 A) handles motor inrush without tripping. Breaking capacity is 50 kA Icu per EN/IEC 60947-2 across 12–415 V AC, and 10 kA Icn per EN/IEC 60898-1 at 400 V — so it's rated for both industrial (60947-2) and domestic (60898-1) standards. Overvoltage category IV means it's suitable for main distribution panels, not just sub-circuits. Pollution degree 3 allows use in environments with conductive dust or humidity. The 2-pole version protects both live and neutral, with a separate earth-leakage block available (not included).
Integration notes
Mounts on DIN rail (EN 60715). Double terminals accept 1–25 mm² rigid or 1–16 mm² flexible wire; tighten to 2 N·m. Strip 14 mm of insulation. The toggle provides manual on/off and a trip indicator shows the breaker has opened on fault. IP20 rated — suitable for enclosed panels only. The white housing and compact 36 mm width (4 modules) fit standard distribution boards.