Skip to main content
Schneider Electric A9F05202 — 2-Pole MCB (DIN Rail)

Schneider Electric A9F05202 Acti9 iC60N MCB, 2A Curve D, 2P,

MPNA9F05202
Active

Schneider Electric Acti9 iC60N miniature circuit breaker, A9F05202, 2 A rated current, D curve, 2 poles, 50 kA breaking capacity, thermal-magnetic trip, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F05202 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameIC60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F05202 — Electrical
ParameterValue
Rated current [In]2 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC DC
Network frequency50/60 Hz
A9F05202 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F05202 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F05202 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F05202 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

Rated 2 A continuous, thermal-magnetic trip unit. The magnetic threshold at 12 x In (24 A) handles motor inrush without tripping. Breaking capacity is 50 kA Icu per EN/IEC 60947-2 across 12–415 V AC, and 10 kA Icn per EN/IEC 60898-1 at 400 V — so it's rated for both industrial (60947-2) and domestic (60898-1) standards. Overvoltage category IV means it's suitable for main distribution panels, not just sub-circuits. Pollution degree 3 allows use in environments with conductive dust or humidity. The 2-pole version protects both live and neutral, with a separate earth-leakage block available (not included).

Integration notes

Mounts on DIN rail (EN 60715). Double terminals accept 1–25 mm² rigid or 1–16 mm² flexible wire; tighten to 2 N·m. Strip 14 mm of insulation. The toggle provides manual on/off and a trip indicator shows the breaker has opened on fault. IP20 rated — suitable for enclosed panels only. The white housing and compact 36 mm width (4 modules) fit standard distribution boards.

Frequently asked questions

Where can I buy A9F05202?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings of A9F05202?

Rated current 2 A, D curve (magnetic trip at 12 x In), 2 poles, breaking capacity 50 kA Icu (EN/IEC 60947-2) and 10 kA Icn (EN/IEC 60898-1), thermal-magnetic trip, DIN rail mount, 36 mm wide.

What standards does A9F05202 comply with?

It complies with EN/IEC 60947-2 and EN/IEC 60898-1, and is suitable for isolation per both standards. Pollution degree 3, overvoltage category IV.

MPN