Specifications

Identification

A9F05410 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F05410 — Ratings
ParameterValue
Rated current (In)10 A
Poles configuration4P
Number of protected poles4
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F05410 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F05410 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F05410 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F05410 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F05410 is a 4-pole (4P) miniature circuit-breaker from the Acti9 iC60N series, rated 10 A with a D-curve — magnetic trip at 12 x In (±20 %), so it handles inrush from motor loads, transformers, or welding equipment without nuisance tripping on startup. The thermal-magnetic trip unit covers both overload (thermal bimetal) and short-circuit (solenoid) protection in one package. Breaking capacity hits 36 kA Icu at 12–133 V AC (EN/IEC 60947-2), enough for high-fault panels near substations; derates to 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V. Under EN/IEC 60898-1 it's rated 10 kA Icn at 400 V — the standard for domestic/commercial distribution boards. That dual-standard certification (60947-2 for industrial, 60898-1 for distribution) means it qualifies for either a control-panel feeder or a sub-distribution board.

Snaps onto standard DIN rail — 9 mm pitch occupies 8 modules (72 mm wide), which is the space footprint to budget in your enclosure layout. Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible; strip 14 mm and torque to 2 N·m.

Listed as current-production lifecycle stage. The Acti9 iC60N platform is Schneider's mainstream MCB line.

Frequently asked questions

What is the breaking capacity of A9F05410?

Breaking capacity is 36 kA Icu at 12–133 V AC (EN/IEC 60947-2), 20 kA at 220–240 V, 10 kA at 380–415 V, 6 kA at 440 V, and 10 kA Icn at 400 V (EN/IEC 60898-1).

What curve and rated current does A9F05410 have?

D-curve with magnetic trip at 12 x In (±20 %), rated 10 A. The D-curve is sized for loads with high inrush — motors, transformers, welding plant.

MPN
A9F05410