Skip to main content
Schneider Electric A9F05432 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F05432 Acti9 iC60N MCB, 32A, D Curve, 4

MPNA9F05432
Active

Schneider Electric Acti9 iC60N, A9F05432, miniature circuit breaker, 4P, 32 A, D curve, 36 kA breaking capacity, thermal-magnetic trip.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F05432 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F05432 — Ratings
ParameterValue
Rated current (In)32 A
Poles configuration4P
Number of protected poles4
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F05432 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F05432 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F05432 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F05432 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F05432 is a 4-pole Acti9 iC60N miniature circuit breaker rated at 32 A with a D tripping curve. It uses thermal-magnetic trip technology for distribution applications, protecting against overloads and short circuits.

This MCB is certified to both EN/IEC 60898-1 and EN/IEC 60947-2, giving you flexibility in specifying it for residential, commercial, or industrial panels. The breaking capacity hits 36 kA Icu at 12-133 V AC, 20 kA Icu at 220-240 V AC, 10 kA Icu at 380-415 V AC, and 6 kA Icu at 440 V AC per the 60947-2 standard. Under the 60898-1 standard, it is rated for 10 kA Icn at 400 V AC. The high 36 kA rating at lower voltages means it can handle high-fault scenarios common in industrial control panels fed by large transformers.

Snaps onto a DIN rail (mounting support: DIN rail). Occupies 8 x 9 mm pitches (72 mm wide), with a depth of 78.5 mm and height of 91 mm. The double terminals on top and bottom accept 1-35 mm² rigid or 1-25 mm² flexible cable. The IP20 finger-safe front is standard for enclosed panels. Suitable for isolation per both EN/IEC 60898-1 and EN/IEC 60947-2, with a visible contact position indicator and a trip indicator for local signalling.

Frequently asked questions

What is the breaking capacity of A9F05432?

The breaking capacity is 36 kA Icu at 12-133 V AC, 20 kA Icu at 220-240 V AC, 10 kA Icu at 380-415 V AC, and 6 kA Icu at 440 V AC per EN/IEC 60947-2, plus 10 kA Icn at 400 V AC per EN/IEC 60898-1.

What is the closest alternative to A9F05432 in the Acti9 family?

Within the Acti9 iC60N range, the closest alternative would be a different amperage or curve code variant of the same 4-pole platform. The A9F05432 is a 32 A D-curve unit; a C-curve version (e.g., 32 A C-curve) would share the same footprint and terminal specs but trip at a lower magnetic threshold (5-10 x In vs 10-15 x In for D). Choose the curve based on the connected load's inrush characteristics.

Where can I buy A9F05432 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for your target quantity to receive a current price and lead-time confirmation.

MPN
A9F05432