Skip to main content
Schneider Electric A9F07132 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F07132 Acti9 iC60H MCB, 32 A, 1P, C-Cur

MPNA9F07132
Active

Schneider Electric Acti9 iC60H, A9F07132, 1P, 32 A, C-curve, 42 kA Icu at 12-60 V AC, thermal-magnetic miniature circuit breaker.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07132 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC60H
Poles description1P
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F07132 — Electrical & Protection
ParameterValue
Rated current (In)32 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F07132 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)3.5 N.m top or bottom

Environmental

A9F07132 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F07132 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F07132 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The A9F07132 is a 1-pole Acti9 iC60H miniature circuit breaker rated 32 A with a C-curve magnetic trip (8 x In +/- 20 %). The C-curve means it tolerates moderate inrush — typical for lighting, small motor, and general distribution loads — without nuisance tripping. The 42 kA Icu at 12-60 V AC (EN/IEC 60947-2) gives headroom for high-fault installations; at 230 V AC the Icn is 10 kA per EN/IEC 60898-1, which covers standard domestic and light commercial panel duty. Dual-rated to both the distribution standard (60898-1) and the industrial standard (60947-2), so it qualifies for either spec line without a separate part number.

Deployment context

Snaps onto DIN rail (EN 60715) — 18 mm per pole, so this 1P unit occupies 2 x 9 mm pitches. The IP20 finger-safe terminals accept up to 35 mm² rigid or 25 mm² flexible wire; torque to 3.5 N·m. The toggle handle and trip-indicator flag give local status without opening the panel door.

Frequently asked questions

What is the breaking capacity of A9F07132 at 230 V AC?

At 230 V AC 50/60 Hz the Icn is 10,000 A per EN/IEC 60898-1. Under the industrial standard EN/IEC 60947-2 the Icu is 15 kA at 220-240 V AC.

Where can I buy the A9F07132?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What standards does the A9F07132 comply with?

It is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with suitability for isolation confirmed under both standards. Pollution degree 3 per 60947-2.

MPN