Skip to main content
Schneider Electric A9F07170 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F07170 Acti9 iC60H MCB, 0.5 A, 1P, C Cu

MPNA9F07170
Active

Schneider Electric Acti9 iC60H, miniature circuit breaker, 1P, 0.5 A, C curve, 70 kA Icu at 240 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07170 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC60H
Poles description1P
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F07170 — Electrical & Protection
ParameterValue
Rated current (In)0.5 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F07170 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom

Environmental

A9F07170 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F07170 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F07170 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The A9F07170 is a 1-pole Acti9 iC60H miniature circuit breaker rated at 0.5 A with a C curve (magnetic trip at 8 x In ±20 %). The 70 kA Icu breaking capacity at 240 V AC (per EN/IEC 60947-2) is its real fault-interruption muscle — it can safely interrupt a 70,000 A prospective fault without welding contacts or exploding the case. That rating matters if this breaker sits downstream of a large transformer or in a high-fault-capacity panel; the 10,000 A Icn per EN/IEC 60898-1 is the domestic-standard rating for the same part. Overvoltage category IV and pollution degree 3 mean the breaker is designed for the main distribution board at the service entrance, not just sub-panels. It tolerates the transient overvoltages and conductive dust typical of industrial switchboards. Dual certification to both EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic) gives it a broader application scope than an MCB carrying only one standard.

Deployment and integration

At 18 mm wide (2 x 9 mm pitches), it occupies one modular space in a distribution board. The double terminals accept 1–25 mm² rigid or 1–16 mm² flexible copper; strip length is 14 mm, tighten to 2 N·m. The toggle handle and trip indicator give local visual status. IP20 finger-safe terminals suit enclosed panels — not for wet or washdown environments.

Frequently asked questions

How do I get current pricing and availability for A9F07170?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the closest alternative to A9F07170 in the Acti9 iC60 family?

Within the Acti9 iC60 range, the closest alternative is a variant with a different rated current or curve code. The A9F07170 is a 0.5 A, C-curve, 1-pole unit; a higher-current iC60H (e.g., 1 A or 2 A) shares the same footprint and breaking capacity but changes the thermal trip threshold. No pin-compatible drop-in exists with identical ratings.

What compliance documentation does Schneider provide for A9F07170?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries tropicalisation class 2 per IEC 60068-1 and limitation class 3 per EN/IEC 60898-1. Standard documentation includes the manufacturer's declaration of conformity for these standards.

MPN
A9F07170