Skip to main content
Schneider Electric A9F07302 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F07302 Acti9 iC60H MCB, 3P C-Curve 2A,

MPNA9F07302
Active

Schneider Electric Acti9 iC60H, miniature circuit breaker, 3P, C-curve, 2 A, 70 kA Icu, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07302 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F07302 — Ratings
ParameterValue
Rated current (In)2 A
Poles configuration3P
Number of protected poles3
Breaking capacity70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)70 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F07302 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07302 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F07302 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F07302 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F07302 is a 3-pole Acti9 iC60H miniature circuit breaker with a C-curve, rated at 2 A. It is a thermal-magnetic trip unit designed for distribution applications in AC or DC networks.

This breaker carries a 70 kA Icu at 220...240 V AC and at 380...415 V AC per EN/IEC 60947-2. At 440 V AC the Icu drops to 50 kA, and under the EN/IEC 60898-1 standard its Icn (rated short-circuit capacity) is 10 kA at 400 V AC. The Icn of 10 kA is the value used for domestic/similar installations. It is also rated for isolation — you can use it as a disconnecting means, verified by the contact position indicator that shows when the contacts are open.

Mounting and integration — DIN rail fit

The 3-pole body takes 6 x 9 mm pitches, so the occupied width is 54 mm. Depth is 78.5 mm, height 91 mm. IP20 finger-safe terminals — fine inside a closed panel, not for wet locations. The white colour is standard for the Acti9 range.

Lifecycle stage is current — this is an active, in-production part from Schneider Electric's Acti9 family. Pollution degree 3 means it is rated for the conductive environment inside a typical industrial panel. Overvoltage category IV confirms it can be used at the service entrance or main distribution board. Earth-leakage protection is a separate block — this MCB alone does not provide GFCI; pair it with a Vigic iC60 if needed.

Frequently asked questions

Where can I buy the A9F07302 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the A9F07302's breaking capacity?

It has a 70 kA Icu at 220...240 V AC and at 380...415 V AC per EN/IEC 60947-2, dropping to 50 kA Icu at 440 V AC, and an Icn of 10 kA at 400 V AC per EN/IEC 60898-1.

What compliance documentation does Schneider provide for the A9F07302?

The part is certified to EN/IEC 60947-2 and EN/IEC 60898-1, rated for isolation, and carries IP20 protection. Pollution degree 3 and overvoltage category IV are specified. For RoHS/REACH declarations, refer to Schneider Electric's product compliance portal using the order code.

MPN
A9F07302