Skip to main content
Schneider Electric A9F07313 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F07313 Acti9 iC60H MCB, 13 A, 3P, C Cur

MPNA9F07313
Active

Schneider Electric Acti9 iC60H, miniature circuit-breaker, 13 A, 3P, C curve, 42 kA breaking capacity at 12-133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07313 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F07313 — Ratings
ParameterValue
Rated current (In)13 A
Poles configuration3P
Number of protected poles3
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F07313 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07313 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F07313 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F07313 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F07313 is an Acti9 iC60H miniature circuit-breaker rated 13 A, 3 poles, C curve. It carries a 42 kA Icu breaking capacity at 12–133 V AC and 30 kA at 220–240 V AC, certified to both EN/IEC 60947-2 and EN/IEC 60898-1. That dual-standard rating means it can serve as a distribution board MCB under 60898-1 or as an industrial circuit breaker under 60947-2, giving you flexibility in panel design.

Breaking capacity and curve

The C curve magnetic trip is set at 8 x In ±20 %, so it holds through motor inrush and transformer energisation without nuisance tripping — typical for mixed resistive-inductive loads in distribution panels. The 42 kA Icu at low voltage (12–133 V AC) is unusually high for a 13 A frame; it handles high-fault-current scenarios like large UPS output or DC-link protection. At 400 V AC the Icn under 60898-1 is 10 kA, matching standard domestic-commercial board requirements.

Mounts on DIN rail, 6 modules wide (54 mm). Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible, with a 2 N.m tightening torque and 14 mm strip length. The IP20 finger-safe terminals are standard for enclosed panels.

Frequently asked questions

What is the breaking capacity of A9F07313 at 400 V AC?

Under EN/IEC 60898-1 the Icn is 10 kA at 400 V AC 50/60 Hz. Under EN/IEC 60947-2 the Icu is 15 kA at 380–415 V AC and 10 kA at 440 V AC.

What compliance documentation does this brand provide for A9F07313?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries CE, UKCA, and EAC markings, and is suitable for isolation per both standards. RoHS and REACH declarations are included with the shipment.

Where can I buy A9F07313 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

MPN