Skip to main content
Schneider Electric A9F07410 — Miniature Circuit Breakers (MCB)

A9F07410 Acti9 iC60H MCB, 4P C-curve 10 A, 42 kA

MPNA9F07410
Active

Schneider Electric Acti9 iC60H miniature circuit-breaker, A9F07410, 4P, C-curve, 10 A, 42 kA Icu at 12-133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07410 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F07410 — Ratings
ParameterValue
Rated current (In)10 A
Poles configuration4P
Number of protected poles4
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F07410 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07410 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F07410 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F07410 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F07410 is a 4-pole miniature circuit-breaker from the Acti9 iC60H family, rated 10 A with a C-curve trip characteristic. It's built for distribution panels where you need overcurrent protection on a 4-wire (3-phase + neutral) circuit. Breaking capacity is the headline: 42 kA Icu at 12-133 V AC, 30 kA at 220-240 V, 15 kA at 380-415 V, and 10 kA at 440 V (all per EN/IEC 60947-2). That's a high-interrupting rating for a 10 A MCB — it can clear a fault on a strong transformer-fed bus without welding its contacts. The 15 kA Icn at 400 V per EN/IEC 60898-1 is the standard domestic/commercial rating, but the 60947-2 figures give you the industrial SCCR headroom for panel coordination studies.

Snaps onto a DIN rail (mounting support: DIN rail per). It takes 8 modules of 9 mm pitch (72 mm wide), so plan your enclosure rail space accordingly — that's a 4-pole breaker in a standard 72 mm footprint. Height is 91 mm, depth 78.5 mm; the toggle and trip indicator are on the front face.

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/commercial). That means it qualifies as a circuit-breaker for isolation (suitability for isolation: yes per both standards). Pollution degree 3, overvoltage category IV — rated for the harsh electrical environment at the service entrance or main distribution board.

Frequently asked questions

Where can I buy A9F07410 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm availability and current pricing.

What is A9F07410's breaking capacity at 400 V?

At 400 V AC, the breaking capacity is 15 kA Icu per EN/IEC 60947-2 and 10 kA Icn per EN/IEC 60898-1.

What is the C-curve magnetic trip threshold on this MCB?

The magnetic tripping limit is 8 x In +/- 20 %, so for a 10 A breaker, the magnetic trip occurs between 64 A and 96 A.

MPN
A9F07410