The Schneider Electric A9F07413 is a 4-pole miniature circuit-breaker from the Acti9 iC60H series, rated 13 A with a C-curve trip characteristic. It is dual-rated to both EN/IEC 60947-2 and EN/IEC 60898-1, meaning it carries the higher breaking capacity of an industrial breaker (42 kA Icu at 12...133 V AC) while also meeting the residential/commercial MCB standard. That dual rating is the key spec for a buyer: it lets you use this one part number for distribution panels where you need the SCCR headroom of a 60947-2 device, not just a 60898-1 domestic MCB.
The 42 kA Icu at 133 V AC is the headline figure, but the real-world selectivity picture depends on the voltage on your bus. At 220...240 V AC the Icu drops to 30 kA; at 380...415 V AC it's 15 kA; at 440 V AC it's 10 kA. Under the 60898-1 standard the Icn is 15 kA at 400 V AC. For a 400 V distribution panel, the 15 kA Icu at 415 V is what governs your upstream breaker coordination — that's the figure to plug into your selectivity study, not the 42 kA number.
Height is 91 mm, depth 78.5 mm. The double terminal accepts 1...25 mm² rigid or 1...16 mm² flexible wire; strip length 14 mm, tighten to 2 N.m. IP20 finger-safe front, pollution degree 3 rated, overvoltage category IV. That's a standard panel footprint — no surprises for a panel builder laying out a 4-pole MCB in a distribution board.