Skip to main content
Schneider Electric A9F07432 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F07432 Acti9 iC60H MCB, 32 A, 4P, C-Cur

MPNA9F07432
Active

Schneider Electric Acti9 iC60H, A9F07432, miniature circuit breaker, 4P, 32 A, C-curve, 15 kA Icn at 400 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07432 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F07432 — Ratings
ParameterValue
Rated current (In)32 A
Poles configuration4P
Number of protected poles4
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F07432 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07432 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F07432 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F07432 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F07432 is an Acti9 iC60H miniature circuit breaker (MCB) rated 32 A with a C-curve magnetic trip at 8 x In ±20 % — meaning it holds through moderate inrush (motor start, capacitor bank) and trips fast on a hard short. Four poles (4P) switch all live conductors, so it suits three-phase plus neutral distribution in a panel. The 15 kA Icn at 400 V AC (EN/IEC 60898-1) and 15 kA Icu at 380–415 V AC (EN/IEC 60947-2) tell you it safely interrupts fault currents up to that level without welding contacts or cascading upstream — sized for commercial and light industrial sub-distribution boards where the prospective short-circuit current is known. The thermal-magnetic trip unit combines a bimetal strip for overload protection and a solenoid for short-circuit — no electronic auxiliary power needed, which keeps the trip curve stable across temperature swings inside a warm enclosure.

Snaps onto a DIN rail (mounting support per). The 72 mm width (9 mm pitches × 8) means it occupies eight modular spaces in a distribution board — plan the rail layout accordingly. Double terminals top and bottom accept 1–35 mm² rigid or 1–25 mm² flexible; strip length 14 mm, tighten to 3.5 N·m. The toggle control provides local on/off switching with a trip indicator (red flag) that shows when the breaker has opened on fault — useful for a technician scanning a row of MCBs to find the tripped circuit without metering each one.

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household / similar) — the same breaker covers both installation standards, which simplifies procurement when a panel must meet both a local residential code and an industrial machinery directive.

Frequently asked questions

Where can I buy A9F07432 and how do I get a price?

The A9F07432 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm landed-cost number.

What is A9F07432's breaking capacity at 400 V?

The A9F07432 has a 15 kA Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1, and a 15 kA Icu at 380–415 V AC conforming to EN/IEC 60947-2.

What compliance documentation does Schneider Electric provide for A9F07432?

The A9F07432 is certified to EN/IEC 60947-2 and EN/IEC 60898-1, rated for pollution degree 3, tropicalisation class 2 per IEC 60068-1, and overvoltage category IV. Standard Schneider Electric declarations of conformity and CE/UKCA marking apply.

MPN
A9F07432