Skip to main content
Schneider Electric A9F07450 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F07450 Acti9 iC60H MCB, 50 A C-Curve 4P

MPNA9F07450
Active

Schneider Electric Acti9 iC60H, A9F07450, miniature circuit breaker, 4P, 50 A, C-curve, 42 kA breaking capacity at 12-133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07450 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F07450 — Ratings
ParameterValue
Rated current (In)50 A
Poles configuration4P
Number of protected poles4
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F07450 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07450 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F07450 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F07450 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F07450 is an Acti9 iC60H miniature circuit breaker — a 4-pole, 50 A, C-curve device built for distribution boards and sub-distribution panels. It snaps onto a DIN rail, so panel integration is straightforward: 72 mm wide, 91 mm tall, 78.5 mm deep, occupying 8 x 9 mm pitches on the rail. The C-curve magnetic trip fires at 8 x In ±20 % — meaning it holds through moderate inrush (common with small motors, transformers, or lighting ballasts) and clears fast on a hard short. That 50 A rating on a 4-pole frame handles three-phase plus neutral, rated for distribution duty (Category A per EN/IEC 60947-2). Breaking capacity is the headline number here: 42 kA Icu at 12–133 V AC, 30 kA at 220–240 V, 15 kA at 380–415 V, and 10 kA at 440 V AC (per IEC 60947-2). For IEC 60898-1 the Icn is 15 kA at 400 V AC, so the part is dual-rated and covers both standard families.

Strip length 14 mm, torque to 3.5 N·m. The toggle gives local switching, and the trip indicator shows a clear red/green flag when it's tripped — no guessing from across the panel. Earth-leakage protection is handled by a separate block (Vigi iC60), not integrated — so if you need RCD functionality, plan for the add-on module alongside this breaker on the rail.

Frequently asked questions

What is the breaking capacity of the A9F07450?

42 kA Icu at 12–133 V AC, 30 kA at 220–240 V, 15 kA at 380–415 V, and 10 kA at 440 V AC per IEC 60947-2. Under IEC 60898-1 the Icn is 15 kA at 400 V AC.

What does the C-curve mean on this MCB?

The C-curve magnetic trip fires at 8 x In ±20 %, so it holds through moderate inrush currents from small motors, transformers, or lighting ballasts, then clears fast on a hard short.

MPN
A9F07450