Skip to main content
Schneider Electric A9F68316 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F68316 Acti9 iT60 MCB, 16 A, C Curve, 3

MPNA9F68316
Active

Schneider Electric Acti9 iT60, miniature circuit breaker, 16 A, C curve, 3P, 54 mm, DIN rail, thermal-magnetic, dual standard EN/IEC 60947-2 and 60898-1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68316 — Identification
ParameterValue
Product nameActi9 iT60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F68316 — Ratings
ParameterValue
Rated current (In)16 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F68316 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
A9F68316 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Control typeToggle
Terminal connection typeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Number of 9 mm pitches6
A9F68316 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 %
Tropicalisation class2 conforming to EN/IEC 60068-2-78
A9F68316 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F68316 is a 16 A, 3-pole miniature circuit breaker from Schneider Electric's Acti9 iT60 range, with a C curve (magnetic trip at 8 × In ±20 %). Breaking capacity is dual-rated: 10 kA Icn at 400 V AC per EN/IEC 60898-1 (the household-standard rating), and 10 kA Icu at 380–415 V AC per EN/IEC 60947-2 (the industrial-standard rating).

At 54 mm wide (6 × 9 mm pitches), it occupies three modular spaces — the standard width for a 3-pole MCB. Removable comb busbar installed means it's ready for daisy-chaining line-side feeds across a row of breakers without extra wiring. Tropicalisation class 2 per EN/IEC 60068-2-78 means it withstands 95 % relative humidity — relevant for coastal or unconditioned plant rooms.

No official successor or direct cross-reference exists because it's the active model. If you're maintaining an older panel that used the previous-generation Multi9 or C60 range, the Acti9 iT60 is the direct functional replacement — same footprint, same curve, same breaking capacity class.

Frequently asked questions

Where can I buy the A9F68316 and get a price?

The A9F68316 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your target quantity and delivery window.

What are the key ratings of the A9F68316?

Rated current 16 A, C curve, 3-pole, breaking capacity 10 kA at 400 V AC (Icn per EN/IEC 60898-1 and Icu per EN/IEC 60947-2), thermal-magnetic trip, suitable for isolation, 54 mm wide, DIN rail mount.

What standards does the A9F68316 comply with?

It is dual-rated to EN/IEC 60947-2 (industrial standard) and EN/IEC 60898-1 (household standard). It also carries tropicalisation class 2 per EN/IEC 60068-2-78 and pollution degree 3 per EN/IEC 60947-2.

MPN
A9F68316