Skip to main content
Schneider Electric A9F68450 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F68450 Acti9 iT60 MCB, 50 A, C-Curve, 4

MPNA9F68450
Active

Schneider Electric Acti9 iT60 miniature circuit breaker, 50 A, C-curve, 4 poles, 72 mm wide, breaking capacity 36 kA at 240 V AC, DIN-rail mount, current production.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F68450 — Identification
ParameterValue
Product nameActi9 iT60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F68450 — Ratings
ParameterValue
Rated current (In)50 A
Poles configuration4P
Number of protected poles4
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F68450 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
A9F68450 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeRemovable comb busbar installed
Control typeToggle
Terminal connection typeSingle terminal (top or bottom) 1...35 mm² rigid Single terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Number of 9 mm pitches8
A9F68450 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 B conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 %
Tropicalisation class2 conforming to EN/IEC 60068-2-78
A9F68450 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F68450 is a 4-pole Acti9 iT60 miniature circuit breaker rated 50 A with a C-curve, built for distribution panels where you need a thermal-magnetic trip that handles moderate inrush without nuisance tripping. It's dual-rated to EN/IEC 60947-2 and EN/IEC 60898-1, so the same breaker qualifies for industrial panel (60947-2) and final-distribution (60898-1) duty; the 60947-2 rating gives you the higher short-circuit capacity numbers that matter when you're coordinating with upstream gear in a mine or mill switchroom. The breaking capacity tells the real story: 36 kA Icu at 240 V AC, 20 kA at 240 V, 10 kA at 415 V, and 6 kA at 440 V — all per IEC 60947-2. The 10 kA Icn at 400 V per IEC 60898-1 is the commercial-distribution rating; the 60947-2 numbers are what the panel designer uses for the SCCR declaration on the nameplate.

The removable comb busbar is already accounted for in the mounting mode — you can bus the line side across multiple breakers without extra hardware. Terminals accept 1–35 mm² rigid or 1–25 mm² flexible on a single terminal top or bottom; strip length 14 mm, torque to 3.5 N·m. IP20 B finger-safe terminals keep the panel builder safe during commissioning.

Frequently asked questions

How do I get current pricing and availability for A9F68450?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels; no fixed price or stock count is published here.

What is A9F68450's listed range (Acti9) on this component line?

The A9F68450 belongs to the Schneider Electric Acti9 range, specifically the iT60 series of miniature circuit breakers for distribution applications.

What is A9F68450's listed width (72 mm) on this component line?

The A9F68450 is 72 mm wide, which corresponds to 8 × 9 mm DIN-rail pitches. That's standard for a 4-pole MCB — each pole takes 18 mm (2 pitches).

What compliance documentation does this brand provide for A9F68450 (RoHS, REACH, UL, IEC)?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. The manufacturer typically provides a declaration of conformity covering these standards; RoHS and REACH compliance documentation is available on request from the brand's documentation portal.

MPN