Schneider Electric A9F77325 — Miniature Circuit Breakers (MCB)

A9F77325 Acti9 iC60N MCB, 25 A, 3P, C-Curve, 36 kA

MPNA9F77325
Active

Schneider Electric Acti9 iC60N, A9F77325, miniature circuit breaker, 25 A, 3P, C-curve, 36 kA Icu at 12-133 V AC, DIN rail mount.

$74.01Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F77325 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F77325 — Ratings
ParameterValue
Rated current (In)25 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F77325 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F77325 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeFixed
Control typeToggle
Terminal connection typeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height85 mm
Depth78.5 mm
Number of 9 mm pitches6
A9F77325 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F77325 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

What the ratings mean for fit

The A9F77325 is a 25 A rated, 3-pole miniature circuit breaker from the Acti9 iC60N range. The C-curve (magnetic trip at 8 x In ±20%) means it handles moderate inrush from motor starters, small transformers, and lighting banks without nuisance tripping — a typical choice for general distribution circuits in commercial and light industrial panels. Breaking capacity is the headline number that decides whether this breaker holds in a high-fault location. At 36 kA Icu (12–133 V AC) it clears severe faults near the service entrance; at 20 kA (220–240 V) it covers most panelboard mains; at 10 kA (380–415 V) it suits sub-distribution boards. The 6 kA rating at 440 V AC is the tail-end — verify the available fault current at the installation point before committing the BOM line. Dual-rated to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household / commercial), so it qualifies for either duty class. Pollution degree 3 and overvoltage category IV mean it's rated for the harsh electrical environment of a main distribution board — not just a clean sub-panel.

Panel integration and mounting

Snaps onto a standard DIN rail (mounting support per). The 54 mm width × 85 mm height × 78.5 mm depth footprint occupies 6 x 9 mm pitches — count the rail space before laying out a multi-pole group. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible; strip length 14 mm, torque to 2 N·m. IP20 finger-safe terminals suit enclosed panels; no washdown rating here.

Frequently asked questions

What is A9F77325's breaking capacity at 400 V?

At 380–415 V AC the Icu is 10 kA per EN/IEC 60947-2. Under EN/IEC 60898-1 the Icn is 6 kA at 400 V AC.

MPN