Schneider Electric A9FDB606 — 1-Pole MCB (DIN Rail)

Schneider Electric A9FDB606 Acti9 iDPN N Arc, 6A C-curve AFD

MPNA9FDB606
Obsolete

Schneider Electric Acti9 iDPN N Arc, arc fault detection circuit breaker (AFDD), 1P+N, 6 A rated current, C-curve, 6 kA breaking capacity, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9FDB606 — Identification
ParameterValue
Product nameActi9 iDPN N Arc
Product / component typeArc fault detection circuit breaker
Product rangeActi9
Device short nameiDPN N Arc
Poles description1P + N
Number of protected poles1
A9FDB606 — Electrical & Protection
ParameterValue
Rated current (In)6 A at 30 °C
Rated operational voltage (Ue)230 V AC 50 Hz conforming to IEC 62606 230 V AC 50 Hz conforming to EN/IEC 60898-1
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9FDB606 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal for 1 cable(s) 10 mm² flexible Tunnel type terminal for 2 cable(s) 2.5 mm² flexible Tunnel type terminal for 1 cable(s) 16 mm² rigid Tunnel type terminal for 2 cable(s) 2.5 mm² rigid
Mounting supportDIN rail
Mounting modeClip-on
Width36 mm
Height81 mm
Depth72 mm
Tightening torque (by circuit)2 N.m
A9FDB606 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9FDB606 — Approvals
ParameterValue
Conformity standardsEN/IEC 62606 IEC 60898-1
A9FDB606 — Electrical
ParameterValue
[Ui] rated insulation voltage400 V AC
[Uimp] rated impulse withstand voltage4 kV conforming to IEC 60898-1

Product details

Arc fault detection circuit breaker, 6 A C-curve, 1P+N

The Schneider Electric A9FDB606 is an Acti9 iDPN N Arc arc fault detection circuit breaker (AFDD) combining overcurrent protection with series arc-fault detection in a single 1P+N module. Rated 6 A at 30 °C with a C-curve magnetic trip (5...10 x In), it breaks 6000 A Icn at 230 V AC 50 Hz per EN/IEC 60898-1. The thermal-magnetic trip unit covers overload and short-circuit; the arc-fault electronics detect hazardous series arcing downstream and trip the circuit independently of the overcurrent mechanism.

The 6 kA breaking capacity at 230 V AC is the maximum fault current it can safely interrupt; this matches typical domestic and light commercial panel fault levels (IEC 60898-1). Limitation class 3 means it restricts let-through energy under short-circuit, reducing stress on downstream wiring and devices.

Clip-on mounting to DIN rail, 36 mm wide (2 modular spaces), 81 mm tall, 72 mm deep. Neutral on the left, phase on the right — tunnel terminals accept up to 16 mm² rigid or 10 mm² flexible (single cable), or 2.5 mm² for two cables. Tightening torque 2 N·m, strip length 14 mm. The 9 mm pitch between phase and neutral terminals matches standard Acti9 busbar spacing.

Frequently asked questions

What is the breaking capacity of A9FDB606?

The A9FDB606 has a breaking capacity of 6000 A Icn at 230 V AC 50 Hz, conforming to EN/IEC 60898-1.

Where can I buy A9FDB606 and how is it quoted?

The A9FDB606 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What standards does A9FDB606 comply with?

The A9FDB606 complies with EN/IEC 62606 (arc fault detection devices) and IEC 60898-1 (circuit-breakers for overcurrent protection).

MPN