Skip to main content
Schneider Electric A9K23601 — 1-Pole MCB (DIN Rail)

Schneider Electric A9K23601 Acti9 iK60 MCB, 1A Curve B, 1P+N

MPNA9K23601
Obsolete

Schneider Electric Acti9 iK60 miniature circuit-breaker, A9K23601, 1P+N, 1 A rated, B-curve, 6 kA breaking capacity at 230 V AC, thermal-magnetic trip, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9K23601 — Identification
ParameterValue
Product nameActi9 iK60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiK60N
Poles description1P + N
Number of protected poles1
Device applicationDistribution
A9K23601 — Electrical & Protection
ParameterValue
Rated current (In)1 A at 30 °C
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9K23601 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeSingle terminal (top or bottom) 1...25 mm² rigid
Mounting supportDIN rail
Mounting modeClip-on
Width36 mm
Height85 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9K23601 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9K23601 — Approvals
ParameterValue
Conformity standardsEN/IEC 60898-1
A9K23601 — Electrical
ParameterValue
[Ui] rated insulation voltage440 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60898-1

Product details

The Schneider Electric A9K23601 is a 1P+N miniature circuit-breaker from the Acti9 iK60 series, rated 1 A at 30 °C with a B-curve (magnetic trip between 3 and 5 x In).

The 1 A rating and B-curve mean it trips fast on moderate overloads (3–5 x In), so it suits resistive loads like lighting strings or control transformers where inrush is low. Thermal-magnetic trip technology handles both sustained overload (thermal bimetal) and short-circuit (solenoid). It is also certified for isolation (EN/IEC 60898-1), meaning you can safely isolate the downstream circuit with the toggle in the OFF position. The 1P+N configuration switches the phase and switches the neutral (neutral left). Only the phase is protected — the neutral is switched but not monitored for overcurrent.

IP20 finger-safe protection on the front; the terminals are protected when wired.

Frequently asked questions

What is the breaking capacity of the A9K23601?

The A9K23601 has a breaking capacity of 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1. This is the standard domestic/commercial fault level for this standard.

What is the A9K23601 used for?

The A9K23601 is a miniature circuit-breaker for distribution applications — typically protecting lighting circuits, small control transformers, or resistive loads on a single-phase 230 V AC supply. The 1 A B-curve rating suits circuits with low inrush current.

Where can I buy the A9K23601?

The A9K23601 is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What compliance standards does the A9K23601 meet?

The A9K23601 is certified to EN/IEC 60898-1 for miniature circuit-breakers, with limitation class 3. Rated insulation voltage 440 V AC, overvoltage category III, pollution degree 2. IP20 front protection per IEC 60529.

MPN