Skip to main content
Schneider Electric A9L2F900 — Fuses & Fuse Holders

Schneider Electric A9L2F900 iPRD F40r Cartridge, Type 2+3, 4

MPNA9L2F900
Active

Schneider Electric Acti9 iPRD F40r, Type 2+3 surge protection cartridge, 40 kA max discharge, < 25 ns response, 18 mm wide, plug-in mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9L2F900 — Identification
ParameterValue
Product / component typeCartridge
Product rangeActi9
A9L2F900 — Ratings
ParameterValue
Rated operational voltage (Ue)240 V AC 50/60 Hz
A9L2F900 — Environmental
ParameterValue
Storage ambient temperature-40...85 °C
IP protection ratingIP20
A9L2F900 — Mechanical
ParameterValue
Mounting supportInto SPD module
Width18 mm
Depth57.2 mm
Height45 mm
A9L2F900 — Approvals
ParameterValue
Standards / approvalsIEC 61643-11:2011 EN 61643-11:2012 EN 61643-11:2018/A11
A9L2F900 — Specifications
ParameterValue
Surge arrester class typeType 2 + 3
Device short nameiPRD F40r
Surge arrester typeElectrical distribution network
A9L2F900 — Electrical
ParameterValue
Nominal discharge currentDifferential mode: 20 kA (L/N)
Maximum discharge currentDifferential mode: 40 kA L/N
Maximum [Up] voltage protection levelDifferential mode <1.5 kV L/N

Product details

The Schneider Electric A9L2F900 is an iPRD F40r surge protection cartridge from the Acti9 range, rated as Type 2+3 per IEC 61643-11. It handles a maximum discharge current of 40 kA in differential mode (L/N) and responds in under 25 ns, clamping the voltage protection level to below 1.5 kV. The integrated fuse means no separate external overcurrent protection is needed for the SPD circuit — one less part to spec and panel-wire.

Type 2+3 classification means this cartridge handles both main distribution board surges (Type 2, 8/20 µs wave) and equipment-level protection (Type 3, combined wave). The 40 kA max discharge (Imax) tells you it can absorb a single high-energy strike without failing; the 20 kA nominal discharge (In) is the rating for repeated events over the product's life. The < 25 ns response time is typical for MOV-based suppressors; it clips fast enough to protect sensitive electronics like PLC power supplies or VFD control boards. The temporary overvoltage (TOV) ratings — 337 V for 5 s withstand, 442 V for 120 min safe failure mode — tell you the cartridge survives a sustained overvoltage event (e.g., a lost neutral) without catching fire, transitioning to a fail-safe short rather than catastrophic rupture.

This cartridge plugs into the iPRD F40r 3P or 3P+N base module (sold separately). The 18 mm width matches a single DIN-rail pitch; two pitches (9 mm each) are occupied. It's designed for TT, TN-S, and TN-C earthing systems, covering most commercial and industrial distribution panels in Europe and markets following IEC wiring rules.

Frequently asked questions

How do I get current pricing and availability for A9L2F900?

Submit an RFQ through this listing. Pricing and stock levels are confirmed at quote time through our independent distribution network — no automated stock figures are shown here.

What is A9L2F900's listed depth (57.2 mm) on this component line?

The listed depth is 57.2 mm, which is the dimension from the DIN-rail mounting face to the front of the cartridge when plugged into the base.

What is A9L2F900's listed width (18 mm) on this component line?

The width is 18 mm, occupying two 9 mm DIN-rail pitches. This is standard for a single-pole SPD cartridge in the Acti9 range.

What compliance documentation does this brand provide for A9L2F900 (RoHS, REACH, UL, IEC)?

The cartridge is certified to IEC 61643-11:2011 and EN 61643-11:2012/A11. The evidence does not list RoHS, REACH, or UL marks; check the manufacturer's declaration for those.

MPN