A9N18353 — Identification
ParameterValue
Product nameActi9 C120
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9N18353 — Ratings
ParameterValue
Rated current (In)80 A at 30 °C
Poles configuration4P
Number of protected poles4
Breaking capacity10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)7500 A 75 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 500 V DC
Rated operational voltage (Ue)380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
A9N18353 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit3...5 x In
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IEC 60947-2
Limitation class3 conforming to EN/IEC 60947-2
Electrical durability (cycles)5000 cycles conforming to IEC 60947-2
Mechanical durability (cycles)20000 cycles
A9N18353 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Control typeToggle
Terminal connection typeTunnel type terminals1...50 mm² rigid Tunnel type terminals1.5...35 mm² flexible
Terminal tightening torque3.5 N.m
Wire stripping length15 mm
Contact position indicatorYes
Local signalling/indicationON/OFF indication
Width108 mm
Height81 mm
Depth73 mm
Number of 9 mm pitches12
A9N18353 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9N18353 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9N18353 is a 4-pole miniature circuit-breaker from the Acti9 C120N series, rated 80 A at 30 °C with a B-curve trip characteristic (magnetic tripping between 3 and 5 times In). It is a thermal-magnetic device, meaning the bimetal handles overloads and the solenoid handles short-circuits — no electronics to drift or fail in high ambient heat. The 10 kA Icn at 400 V AC (per EN/IEC 60898-1) and up to 20 kA Icu at 240 V AC (per EN/IEC 60947-2) tell you it can clear a fault without welding contacts or venting arc gas into the panel, which matters when you are coordinating downstream breakers in a distribution board.

Clip-on mounting on a 35 mm symmetrical DIN rail, 12 module pitches wide (108 mm). Tunnel terminals accept up to 50 mm² rigid or 35 mm² flexible cable; stripping length is 15 mm, torque to 3.5 N·m.

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household/commercial). Suitability for isolation is confirmed (IEC 60947-2). Lifecycle status is current production.

Frequently asked questions

What is the breaking capacity of the A9N18353?

10 kA Icn at 400 V AC per EN/IEC 60898-1, and up to 20 kA Icu at 240 V AC per EN/IEC 60947-2. At 440 V AC the Icu is 6 kA; at 380-415 V AC it is 10 kA. For DC circuits up to 500 V DC the Icu is 10 kA.

What compliance documentation does Schneider provide for A9N18353?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. Tropicalisation class 2 per IEC 60068-1 is listed. RoHS, REACH, and UL documentation should be available from Schneider Electric's product documentation portal.