Skip to main content
Schneider Electric A9N18413 — 2-Pole MCB (DIN Rail)

Schneider Electric A9N18413 Acti9 C120H MCB, 80 A B-Curve 2P

MPNA9N18413
Active

Schneider Electric Acti9 C120H miniature circuit breaker, A9N18413, 80 A rated, B-curve, 2-pole, 15 kA breaking capacity at 400 V AC, thermal-magnetic trip, clip-on 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

A9N18413 — Identification
ParameterValue
Product nameActi9 C120
Series / familyActi9
Device short nameC120H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N18413 — Electrical
ParameterValue
Rated current [In]80 A at 30 °C
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
A9N18413 — Protection
ParameterValue
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu)15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity [Ics]7500 A 50 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Energy limitation class3 conforming to EN/IEC 60947-2
Suitable for isolationYes conforming to IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N18413 — Mechanical
ParameterValue
9 mm pitches6
Width54 mm
Height81 mm
Depth73 mm
Mounting support35 mm symmetrical DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals1...50 mm² rigid Tunnel type terminals1.5...35 mm² flexible
Terminal tightening torque3.5 N.m
Comb busbar / distribution block compatibilityYES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N18413 — Environmental
ParameterValue
Operating temperature range-30...60 °C
Storage temperature range-40...70 °C
Relative humidity95 % at 55 °C
A9N18413 — Approvals
ParameterValue
Standards / complianceEN/IEC 60898-1 EN/IEC 60947-2

Product details

The Schneider Electric A9N18413 is an Acti9 C120H miniature circuit breaker (MCB) rated 80 A at 30 °C with a B-curve trip characteristic (magnetic tripping between 3 and 5 x In). The headline breaking capacity is 15 kA Icn at 400 V AC 50/60 Hz per EN/IEC 60898-1, with an Icu of 10 kA at 440 V AC and 30 kA at 220–240 V AC per EN/IEC 60947-2. This dual-standard rating means the breaker is certified for both residential (60898-1) and industrial (60947-2) fault-clearing requirements, giving the specifying engineer flexibility in panel design without swapping hardware.

Mounts via clip-on to 35 mm DIN rail — standard for panel and enclosure integration. The 54 mm width (9 mm pitch × 6) occupies six modular spaces, which is typical for a 2-pole 80 A MCB in the Acti9 range. Tunnel-type terminals accept 1–50 mm² rigid or 1.5–35 mm² flexible conductors; wire strip length is 15 mm, tightening torque 3.5 N·m. IP20 finger-safe protection is suitable for enclosed panels.

Dual-certified to EN/IEC 60898-1 (MCB standard for household and similar installations) and EN/IEC 60947-2 (low-voltage switchgear and controlgear standard for industrial application). This dual certification is the key differentiator: the same breaker satisfies both a domestic distribution board spec and an industrial panel SCCR study. Electrical durability is 5,000 cycles (IEC 60947-2), mechanical durability 20,000 cycles. Earth-leakage protection requires a separate block (not integrated).

Frequently asked questions

What is the breaking capacity of A9N18413?

The A9N18413 has a breaking capacity of 15 kA Icn at 400 V AC per EN/IEC 60898-1, and an Icu of 10 kA at 440 V AC, 15 kA at 380–415 V AC, and 30 kA at 220–240 V AC per EN/IEC 60947-2.

What standards does A9N18413 comply with?

The A9N18413 is dual-certified to EN/IEC 60898-1 and EN/IEC 60947-2, covering both household and industrial switchgear standards.

Where can I buy A9N18413?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the rated current of A9N18413?

The rated current (In) is 80 A at 30 °C, with a B-curve trip characteristic (magnetic trip between 3 and 5 x In).

MPN
A9N18413