The 6 kA breaking capacity (Icn at 220...240 V AC, 50/60 Hz, per EN/IEC 61009-2-1) covers the majority of residential and light commercial fault levels. Clip-on mounting to DIN rail, with a 77.5 mm depth that fits standard modular enclosures.
The C-curve (5...10 x In magnetic trip) means this RCBO is suited for circuits with moderate inrush — lighting, general-purpose sockets, small motor loads — where a B-curve would nuisance-trip but a D-curve would be too slow for fault clearance. The 6 kA breaking capacity at 230 V is the standard domestic/commercial rating; if your installation requires 10 kA or higher SCCR, step up to the Acti9 iC60 range. The 1P+N configuration switches the phase and monitors neutral current for earth-leakage detection, but does not switch the neutral — verify that your distribution scheme expects a switched phase only. The thermal-magnetic trip unit is non-interchangeable, so the 10 A rating is fixed at ordering.
Clip-on to DIN rail (EN 60715). Tunnel terminals top and bottom accept 0.75...16 mm² rigid or 0.33...10 mm² flexible (with or without ferrule); tighten to 2 N·m. Strip length 15 mm. Neutral is on the left. Pollution degree 3, overvoltage category III per IEC 60364, meaning it's rated for fixed installations with transient overvoltages up to 4 kV.