Skip to main content
Schneider Electric A9N1P02DGN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P02DGN Acti9 MCB, 2A D-Curve, 1P, 10k

MPNA9N1P02DGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N1P02DGN, 2 A rated current, D-curve, 1-pole, 10 kA breaking capacity, clip-on 35 mm DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P02DGN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P02DGN — Electrical & Protection
ParameterValue
Rated current (In)2 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Tripping curve codeD
Magnetic tripping limit10...14 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P02DGN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)2 N.m
A9N1P02DGN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P02DGN — Approvals
ParameterValue
Conformity standardsIS/IEC 60898-1

Product details

The Schneider Electric A9N1P02DGN is a 2 A, D-curve miniature circuit breaker from the Acti9 xC60 range, designed for distribution applications where high inrush currents are expected — motor, transformer, or lighting ballast loads that would nuisance-trip a C-curve device. Its thermal-magnetic trip unit responds to sustained overloads via the bimetal element and to short-circuit faults via the solenoid, with magnetic tripping set at 10 to 14 times In (20 to 28 A). The 10 kA breaking capacity at 240 V AC (IS/IEC 60898-1) means it can safely interrupt fault currents up to that level without welding contacts or cascading upstream — essential for coordination in a panel fed by a transformer with moderate fault current.

The 18 mm width occupies two 9 mm pitches — a single-pole breaker that fits a standard modular enclosure slot. Depth of 77.5 mm and height of 85 mm leave clearance for wiring and cover. Tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible conductors; wire stripping length is 13 mm for top or bottom connection. IP20 finger-safe protection is standard for panel-mount breakers — no additional shrouding needed inside a closed enclosure.

Frequently asked questions

Where can I buy A9N1P02DGN and how do I get a price?

The A9N1P02DGN is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is A9N1P02DGN's listed depth?

The listed depth is 77.5 mm.

What is A9N1P02DGN's listed range?

The product range is Acti9, specifically the xC60 series.

What compliance documentation does this brand provide for A9N1P02DGN?

The breaker is certified to IS/IEC 60898-1 and meets tropicalisation class 2 per IEC 60068-1. It carries IP20 protection and pollution degree 3 rating.

MPN