Schneider Electric A9N1P03CIN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P03CIN Acti9 xC60 MCB, 3 A, 1P, C-Cur

MPNA9N1P03CIN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N1P03CIN, 1-pole, 3 A, C-curve, 10 kA breaking capacity at 240 V AC, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N1P03CIN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P03CIN — Electrical & Protection
ParameterValue
Rated current (In)3 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz 12...48 V DC 60 V DC
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P03CIN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)2 N.m
A9N1P03CIN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P03CIN — Approvals
ParameterValue
Conformity standardsIS/IEC 60947-2
A9N1P03CIN — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IS/IEC 60947-2
[Uimp] rated impulse withstand voltage4 kV conforming to IS/IEC 60947-2

Product details

The Schneider Electric A9N1P03CIN is a 1-pole miniature circuit breaker from the Acti9 xC60 series, rated 3 A with a C-curve trip characteristic. Breaking capacity is 10 kA Icu at 240 V AC, 15 kA at 12–48 V DC, and 6 kA at 60 V DC, all per IS/IEC 60947-2.

The 3 A C-curve is the key selection gate: C-curve trips magnetically at 5–10 x In (here 15–30 A), so it handles moderate inrush from small transformers, lighting ballasts, or control circuits without nuisance trips. The thermal-magnetic trip unit means bimetal for overload, solenoid for short — no electronics to drift. Overvoltage category IV means this breaker is rated for the mains supply entry point — it can handle the transient energy at the service entrance, not just downstream sub-panels. Suitability for isolation per IS/IEC 60947-2 means you can safely use it as a disconnecting means for the downstream circuit during maintenance, provided it's locked off.

Wire strip length is 13 mm for top or bottom connection. IP20 finger-safe terminals — fine inside a locked panel, not for wet locations.

Frequently asked questions

Where can I buy A9N1P03CIN and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position.

What is A9N1P03CIN's breaking capacity?

Breaking capacity is 10 kA Icu at 220–240 V AC, 15 kA at 12–48 V DC, and 6 kA at 60 V DC, all per IS/IEC 60947-2.

What standards does A9N1P03CIN comply with?

It complies with IS/IEC 60947-2, with tropicalisation class 2 per IEC 60068-1 and limitation class 3.

MPN