Skip to main content
Schneider Electric A9N1P32CGN — 1-Pole MCB (DIN Rail)

Schneider Electric A9N1P32CGN Acti9 xC60 MCB, 32 A, C-Curve,

MPNA9N1P32CGN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, 1-pole, 32 A, C-curve, 10 kA breaking capacity, IS/IEC 60898-1, for 35 mm DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N1P32CGN — Identification
ParameterValue
Product nameXC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short namexC60
Poles description1P
Number of protected poles1
Device applicationDistribution
A9N1P32CGN — Electrical & Protection
ParameterValue
Rated current (In)32 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9N1P32CGN — Mounting & Connection
ParameterValue
Terminal connections / wire rangeBiconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid
Mounting support35 mm DIN rail
Mounting modeClip-on
Width18 mm
Height85 mm
Depth77.5 mm
Tightening torque (by circuit)3.5 N.m
A9N1P32CGN — Environmental
ParameterValue
Operating ambient temperature-30...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
A9N1P32CGN — Approvals
ParameterValue
Conformity standardsIS/IEC 60898-1

Product details

The Schneider Electric A9N1P32CGN is a 1-pole Acti9 xC60 miniature circuit breaker rated at 32 A with a C-curve magnetic trip characteristic (5...10 x In). Breaking capacity is 10 kA Icn at 240 V AC, certified to IS/IEC 60898-1, which covers the standard for household and similar installations in India and other IEC markets.

A B-curve would trip too early on those loads; a D-curve would let them ride through but might not clear a hard fault fast enough. Thermal-magnetic trip technology handles both overload (thermal bimetal, slow response) and short-circuit (magnetic solenoid, instantaneous). Overvoltage category IV confirms it's suitable for the main distribution point, not just downstream sub-circuits.

The Biconnect tunnel terminals at the bottom accept up to 25 mm² flexible or 35 mm² rigid cable — that's generous for a 32 A breaker and makes it straightforward to land larger tails or loop through. Wire stripping length is 13 mm for top or bottom connection. The toggle gives clear ON/OFF indication and a contact position indicator shows the actual state of the contacts, not just the handle position — useful during commissioning when you need to confirm isolation visually.

Frequently asked questions

What is the breaking capacity of A9N1P32CGN?

10 kA Icn at 240 V AC 50/60 Hz, conforming to IS/IEC 60898-1. That's the standard rating for household-type MCBs in this class.

What does the C-curve mean on this breaker?

The magnetic trip operates between 5 and 10 times the rated current. For the 32 A version, that's 160–320 A instantaneous trip — suited for circuits with moderate inrush, like small motor loads or groups of fluorescent fittings.

Where can I buy A9N1P32CGN and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here.

MPN