Skip to main content
Schneider Electric A9N26612 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9N26612 Vigi xC60 RCD Add-on, 2P 63A AC

MPNA9N26612
Active

Schneider Electric Acti9 Vigi xC60 add-on residual current device, A9N26612, 2P, 63 A, 100 mA, Type AC, instantaneous, DIN rail clip-on.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9N26612 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyElectromechanical Voltage independent
Local signalling / indicationRed indicator light on the front face
A9N26612 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)230...240 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...240 V conforming to EN/IEC 61009-2-1
Poles description2P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Device location in systemOutgoer
A9N26612 — Identification
ParameterValue
Product / component typeAdd-on residual current device
Product range / familyActi9
Device short nameVigi xC60
A9N26612 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Width in 9 mm modules4
Terminal connectionsTunnel type terminal downside for 1 cable(s) 1...35 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible with cable end
Wire stripping length14 mm for bottom connection
Terminal tightening torque3.5 N.m bottom
Width72 mm
Height87 mm
Depth74.5 mm
A9N26612 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9N26612 — Approvals
ParameterValue
StandardsEN/IEC 61009-1 EN/IEC 61009-2-1

Product details

The Schneider Electric A9N26612 is a Vigi xC60 add-on residual current device (RCD) from the Acti9 range, designed to bolt onto the outgoing side of a compatible MCB via screw terminals. It is a 2-pole unit rated for 63 A continuous current with a 100 mA earth-leakage sensitivity, Type AC (sinusoidal AC residual currents only). The trip mechanism is electromechanical and voltage-independent — it clears a ground fault even if the phase voltage collapses, which matters for circuits where the neutral reference could be lost.

63 A at 230-240 V AC means this block handles the full current of a 63 A breaker downstream — no derating needed for the RCD itself at that load. The 100 mA sensitivity is less common than 30 mA; it is specified for circuits where nuisance tripping from normal leakage (long cable runs, heater elements, IT equipment) would be a problem, while still providing earth-fault protection. Type AC means it detects only sinusoidal AC residual currents — not pulsed DC or smooth DC — so it is not suitable for circuits with VFDs, UPS outputs, or EV chargers that generate DC fault currents.

Clip-on mounting to DIN rail, 4 modules wide (72 mm). The 74.5 mm depth fits standard Acti9 enclosures. Bottom tunnel terminals accept 1 to 35 mm² rigid or 1 to 25 mm² flexible cable; strip length 14 mm, tighten to 3.5 N·m. The red indicator on the front shows tripped status. IP20 on the body, IP40 inside a modular enclosure — fine for dry indoor panels, not for washdown areas.

Frequently asked questions

What is the earth leakage sensitivity and type of A9N26612?

100 mA, Type AC (sinusoidal AC residual currents only), instantaneous trip, voltage-independent electromechanical design.

What is the rated current and voltage for A9N26612?

63 A rated current at 230-240 V AC, 50/60 Hz, 2-pole.

What compliance standards does A9N26612 meet?

Designed to EN/IEC 61009-1 and EN/IEC 61009-2-1. Rated insulation voltage 500 V AC, impulse withstand 6 kV, pollution degree 3.

Where can I buy A9N26612?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
A9N26612