Skip to main content
Schneider Electric A9N2P04CIN — 2-Pole MCB (DIN Rail)

Schneider Electric A9N2P04CIN Acti9 xC60 MCB, 4 A C-Curve 2P

MPNA9N2P04CIN
Active

Schneider Electric Acti9 xC60 miniature circuit breaker, A9N2P04CIN, 4 A rated current, C-curve, 2-pole, 10 kA breaking capacity at 400 V AC, clip-on DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9N2P04CIN — Identification
ParameterValue
Product nameXC60
Product rangeActi9
Series / familyActi9
Device short namexC60
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9N2P04CIN — Electrical
ParameterValue
Rated current [In]4 A
Number of protected poles2
Pole configuration2P
Rated operational voltage [Ue]220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC
Network type (AC/DC)AC DC
Network frequency50/60 Hz
A9N2P04CIN — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu)10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2
Rated service breaking capacity [Ics]6 kA conforming to IS/IEC 60947-2 - 100...125 V DC 7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz
Energy limitation class3 conforming to IS/IEC 60947-2
Suitable for isolationYes conforming to IS/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9N2P04CIN — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height85 mm
Depth77.5 mm
Mounting support35 mm DIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)
Terminal tightening torque2 N.m
Comb busbar / distribution block compatibilityTop: YES
Local signalling / indicationON/OFF indication
Contact position indicatorYes
A9N2P04CIN — Environmental
ParameterValue
Operating temperature range-30...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9N2P04CIN — Approvals
ParameterValue
Standards / complianceIS/IEC 60947-2

Product details

The Schneider Electric A9N2P04CIN is an Acti9 xC60 miniature circuit breaker rated at 4 A with a C-curve thermal-magnetic trip unit, meaning it holds 4 A continuous and trips magnetically between 5 and 10 times rated current — standard for general-purpose distribution protecting lighting, socket circuits, and small motor loads in commercial or residential panels. The 10 kA breaking capacity at 380–415 V AC (conforming to IS/IEC 60947-2) means it can safely interrupt a fault current up to that level without welding contacts or cascading upstream — adequate for most building supply points where the prospective short-circuit current stays under 10 kA. The 2-pole configuration (2P) switches both phase and neutral, giving full isolation on the outgoing circuit.

Panel integration and installation notes

The breaker occupies 36 mm width (2 x 18 mm modular pitches), which is two standard DIN-rail module spaces — plan for that when laying out a crowded panel.

Frequently asked questions

Where can I buy the A9N2P04CIN and get a price?

The A9N2P04CIN is available to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not listed here.

What is the breaking capacity of the A9N2P04CIN?

The A9N2P04CIN has a breaking capacity of 10 kA Icn at 380–415 V AC 50/60 Hz conforming to IS/IEC 60947-2, and 6 kA Icu at 100–125 V DC.

What standards does the A9N2P04CIN comply with?

It conforms to IS/IEC 60947-2, the standard for low-voltage circuit breakers used in industrial and commercial distribution.

MPN
A9N2P04CIN